List of error codes for the Saunier Duval Genia Air Genia Hybrid air-to-water heat pump
List of error codes for the Saunier Duval Genia Air Genia Hybrid air-to-water heat pump
Download the Saunier Duval air-to-water heat pump error code guide
| e-bus communication fault with the boiler. | 001 | Check that the unit is connected to the control box The unit is not connected to the control box.
Check the +/- polarity of the connection. The cable polarity is reversed. Check that there is no power The unit is switched off. outage, that the unit is properly plugged in and powered. |
|
| e-bus communication fault with the heat pump. | 002 | ||
| e-bus communication fault with the hydraulic module. | 003 | ||
| Heating circuit flow temperature sensor fault (open circuit). | 010 | The sensor is faulty or not properly connected to the control box
or the hydraulic module. |
Check the sensor connections. Check that the sensor’s position and operation are correct. Check the sensor’s resistance. |
| Circuit flow temperature sensor fault.
Check the heating sensor’s resistance (short circuit). |
011 |
The sensor is short-circuited. |
|
| Low-temperature heating circuit flow temperature sensor fault
(open circuit). |
012 |
The sensor is faulty or not properly connected to the control box. |
|
| Circuit flow temperature sensor fault.
Check the low-temperature heating sensor’s resistance (short circuit). |
013 |
The sensor is short-circuited. |
|
| Domestic hot water tank temperature sensor fault (open circuit). |
014 |
The sensor is faulty or not properly connected to the control box. | |
| Domestic hot water tank temperature sensor fault (short circuit). |
015 |
The sensor is short-circuited. |
|
| Pressure sensor fault. | 020 | The sensor is faulty or not properly connected to the hydraulic module. | |
|
Pressure too low <0.5 bar. |
021 |
There is a leak in the heating circuit. Check for leaks.
Degassing was not done correctly. Bleed the heating circuit. Refill the system. |
|
| Communication fault with the zone 1 wireless room thermostat. |
030 |
The room thermostat is too far from the control box. There is a problem with the room thermostat’s batteries. |
|
| Communication fault with the zone 2 wireless room thermostat. |
031 |
||
| Communication fault with the zone 3 wireless room thermostat. |
032 |
||
| Communication fault with the zone 4 wireless room thermostat. |
033 |
||
| Communication fault with the zone 5 wireless room thermostat. |
034 |
||
| Communication fault with the zone 6 wireless room thermostat. |
035 |
||
|
Communication fault with the wireless outdoor sensor. |
036 |
The outdoor sensor is too far from the control box. |
Check the location of the outdoor sensor. The sensor is powered by a photovoltaic cell.
The outdoor sensor does not have a battery that needs replacing. |
|
Fan speed too low (<300 rpm). |
037 |
The fan speed is too low.
Lockout fault if this occurs more than 3 times in the last 10 startups. |
Check:
– fan connections. – main board fuses. – fan grille obstruction. – fan motor. |
| Compressor suction temperature sensor. | 514 |
Check: – sensor connections. – sensor position and operation. |
|
| Compressor discharge temperature sensor. | 517 | ||
| Glycol water circuit return temperature sensor. | 519 | ||
| Glycol water circuit flow temperature sensor. | 520 |
Check: – sensor connections. – sensor position and operation. |
|
| Evaporation/condensation temperature sensor. | 526 | ||
| Plate heat exchanger temperature sensor. | 528 | ||
|
Glycol water circuit flow too low (<500 l/h) or too high (>1000 l/h). Transient fault. |
532 |
Glycol water circuit flow too low. |
Force the pump and check the flow.
Adjust the water flow using the pump speed or the hydraulic module’s control valve. |
| Glycol water circuit flow too high or incorrect flow reading. | Force the pump and check the flow. | ||
| Insufficient glycol water. | Leak or faulty valve. | ||
| Filter missing or clogged on the glycol water return. | Install a sludge filter. Clean the sludge filter. | ||
|
The expansion tank is faulty. |
Check the expansion tank pressure. Re-pressurize the expansion tank.
Replace the expansion tank. |
||
|
Glycol water circuit flow temperature too high (>54°C). Transient fault. |
534 |
Sensor faulty or disconnected. |
Check:
– sensor connections. – sensor position and operation. |
| Incorrect water flow reading. | Check for water flow by closing a valve on the glycol water circuit. | ||
|
Faulty expansion tank. |
Check the expansion tank pressure. Re-pressurize the expansion tank.
Replace the expansion tank. |
||
| Filter missing or clogged on the glycol water return. | Install a sludge filter. Clean the sludge filter. | ||
| Air present in the glycol water circuit. | Bleed the glycol water circuit. | ||
|
Compressor discharge temperature too high (>105°C). Lockout fault. |
536 |
Refrigerant overcharge or undercharge. | Check for overcharge or undercharge. |
|
Temperature sensor faulty or disconnected. |
Check the discharge sensor connections.
Check that the sensor’s position and operation are correct. Check the sensor’s resistance. |
||
|
Faulty water flow sensor. |
Check for water flow by forcing the pump.
Refer to the “Heat pump circuit flow adjustment” chapter. |
||
| Pre-expansion on the liquid line (pressure drop). | Check for pinched tubing. Clogged refrigerant filter. | ||
|
Faulty electronic expansion valve. |
Check
– that the motor is properly clipped onto the expansion valve body. – that the electronic expansion valve is working properly. If not: – check the winding resistance. – replace the motor. – as a last resort, replace the electronic expansion valve. |
||
| Poor heat exchange in the plate heat exchanger. | Clean the plate heat exchanger. | ||
| Heat pump temperature too high. | Eliminate the heat source or protect the heat pump. | ||
|
Compressor discharge pressure too high (> 42 Bar). Lockout fault. |
537 |
Refrigerant overcharge or undercharge. | See solutions for fault 536. |
| Faulty pressure switch. | Check the pressures with a gauge, replace the pressure switch. | ||
| Faulty pressure switch contact. | Check the pressure switch. | ||
| Faulty cables. | Check the condition of the pressure switch cables. | ||
| Pre-expansion on the liquid line (pressure drop). | See solutions for fault 536. | ||
| Faulty water flow sensor. | See solutions for fault 536. | ||
| Faulty electronic expansion valve. | See solutions for fault 536. | ||
| Poor heat exchange in the plate heat exchanger. | See solutions for fault 536. | ||
| Heat pump temperature too high. | See solutions for fault 536. |
|
Operation outside the compressor envelope (LP >15 Bar or LP <4.5 Bar or HP <11 Bar or HP >42 Bar). Transient fault. |
554 |
Refrigerant overcharge or undercharge. | Check for overcharge or undercharge. |
|
Presence of non-condensables. |
Non-condensables are present if:
– discharge temperature >90°C (with ambient temperature between 0 and 12°C) – high HP pressure and normal LP pressure, – no correlation between pressures and ambient temperature when the compressor has been off for several hours. Recharge the refrigerant. |
||
|
Faulty electronic expansion valve. |
Check the operation of the electronic expansion valve
– check the winding resistance. – check how the expansion valve is clipped on. Replace the motor or the entire expansion valve. |
||
| Pre-expansion on the liquid line (pressure drop). | Check for pinched tubing. | ||
| Poor heat exchange on the plate exchanger. | Check the condition of the plate exchanger. | ||
|
4-way valve is faulty. |
Check the solenoid valve’s power supply. Force defrost mode and check the cycle reversal.
Check the solenoid valve coil. Check the subcooling NTC sensor. Replace the 4-way valve. |
||
| Defrost temperature sensor fault. |
581 |
Faulty or disconnected sensor. |
Check:
– sensor connections. – sensor position and operation. |
| Expansion valve motor fault. | 582 | Faulty or disconnected motor. | Check the motor and its wiring. Replace the motor. |
| Exchanger
à plate too low temperature (<0°C). Erratic fault. |
583 |
Incorrect setting. | Check the control unit’s settings. |
| Temperature sensor incorrectly positioned. | Check the position of the temperature sensors. | ||
|
The compressor discharge temperature hasn’t increased (<5k in 2 minutes). Blocking fault if it occurs 3 times in 4 hours. |
584 |
The compressor isn’t powered. |
Check:
– compressor connections and wiring. – compressor winding resistance. Replace the compressor. |
|
The compressor’s high-pressure sensor is open. |
Check:
– that the 4-way valve isn’t stuck. – that the electronic expansion valve is working properly. |
||
| There’s a refrigerant shortage. | Check for a refrigerant charge shortage. | ||
| Fault on the compressor discharge temperature sensor. | Check the position and contact of the temperature sensor
at the compressor discharge. |
||
| Fault on the pre-expansion temperature sensor.
Blocking fault in cooling mode. |
585 |
Faulty or disconnected sensor. |
Check: – sensor connections. – sensor position and operation. |
| Air inlet temperature sensor fault. | 774 | Faulty or disconnected sensor. |