Daikin self-diagnostic by error code

Do you have a Daikin air-to-water heat pump or a Daikin air-to-air heat pump? Find the problem using the error code on Daikin’s self-diagnostic chart

Download the Daikin self-diagnostic chart by error code

Indoor unit

 

 

Code malfunction

 

Nature of the malfunction

 

Suspected causes

Models
RA SkyAir VRV Monobloc Energy recovery ventilator (HRV) Chiller unit Fan coil unit
A0 External protection device activated The external protection device connected to the T1-T2 terminal block of the indoor unit is activated. ✔ ✔ ✔
A1 Malfunction caused by the indoor unit’s electronic board Faulty indoor unit electronic board External factor (noise, etc.) ✔ ✔ ✔ ✔ ✔ ✔
A3 Malfunction caused by the drain level control system Drain blockage, upward slope, etc. Faulty drain pump

Faulty float switch or short-circuited connector

 

✔

 

✔

 

✔

 

✔

 

✔

A4 Malfunction caused by freeze protection Insufficient water supply Low water temperature setting

Faulty water temperature thermistor

✔ ✔ ✔ ✔ ✔ ✔
A5 High pressure control in heating mode, freeze protection control in cooling mode Clogged indoor unit air filter and short circuit Faulty indoor unit heat exchanger thermistor  

✔

 

✔

 

✔

 

✔

A6 Malfunction caused by the fan motor Broken wires, short circuit, or disconnected connectors on the fan motor harness Faulty fan motor

Faulty indoor unit electronic board

 

✔

 

✔

 

✔

 

✔

 

✔

A7 Malfunction caused by the swing flap motor Faulty swing flap motor

Faulty indoor unit electronic board Faulty connection cable

Faulty airflow direction adjustment flap cam

 

✔

 

✔

A8 Malfunction caused by overcurrent at the AC input or power supply Abnormal supply voltage

Faulty connection on the signal line Faulty wiring

✔ ✔ ✔
A9 Malfunction caused by the electronic expansion valve Faulty electronic expansion valve coil Faulty indoor unit electronic board Faulty relay wires ✔ ✔ ✔ ✔ ✔
AA Overheating of the heating device 26WH activation ✔ ✔
AF Malfunction caused by a humidification system Leak in the humidifier unit (optional accessory) Faulty drain pipe (upward slope, etc.) Faulty indoor unit electronic board ✔ ✔ ✔
AH Malfunction caused by the air filter dust collector Faulty dust collection element Dirty insulation component

Faulty high-voltage power unit Faulty indoor unit electronic board

 

✔

 

✔

 

✔

 

✔

AJ Malfunction caused by the power setting (indoor unit electronic board) The power setting adapter was not installed when the electronic board was replaced.

Faulty indoor unit electronic board

✔ ✔ ✔
C1 Transmission failure (between the indoor unit’s

electronic board and the secondary electronic board)

Faulty connector connection on the indoor unit’s electronic board  

✔

 

✔

C4 Malfunction caused by the heat exchanger liquid pipe thermistor Faulty liquid pipe thermistor Faulty indoor unit electronic board Faulty connector contact ✔ ✔ ✔ ✔ ✔ ✔ ✔
C5 Malfunction caused by the heat exchanger gas pipe thermistor Faulty gas pipe thermistor

Faulty indoor unit electronic board Faulty connector contact

✔ ✔ ✔ ✔ ✔
C6 Malfunction caused by the fan motor sensor or fan control motor Faulty fan electronic board Faulty power setting adapter connection

On-site setting error

 

✔

 

✔

C7 Fault in the front panel drive motor Faulty front panel drive motor Faulty limit switch ✔
C9 Malfunction caused by the intake air thermistor Faulty intake pipe thermistor Faulty indoor unit electronic board Faulty connector contact ✔ ✔ ✔ ✔ ✔ ✔
CA Malfunction caused by the discharge air thermistor Faulty discharge air thermistor Faulty indoor unit electronic board Faulty connector contact ✔ ✔ ✔ ✔
Malfunction caused by the humidity sensor circuit Faulty humidity sensor Faulty connector contact ✔ ✔ ✔
CJ Room temperature thermistor fault in the remote control Faulty room temperature thermistor in the remote control

Faulty remote control electronic board External factor (noise, etc.)

 

✔

 

✔

 

✔

 

✔

 

✔

Outdoor unit

 

Code malfunction

 

Nature of the malfunction

 

Suspected causes

Models
RA SkyAir VRV Monobloc Energy recovery ventilator (HRV) Chiller unit Fan coil unit
Outdoor unit E0 Protection devices activated (unified) The protection device connected to the outdoor unit’s electronic board is activated.

Faulty contact on the protection device connector

✔ ✔ ✔
E1 Faulty outdoor unit electronic board Faulty outdoor unit electronic board Faulty connection of indoor/outdoor relay wires ✔ ✔ ✔ ✔ ✔
E3 High pressure switch activated Dirty outdoor unit heat exchanger Faulty high pressure switch

Blocked refrigerant piping Faulty connector contact

✔ ✔ ✔ ✔
E3 Circuit No. 1

High pressure switch activated

Dirty outdoor unit heat exchanger Insufficient water supply

Blocked refrigerant piping Faulty connector contact Faulty high pressure sensor

✔
E4 Low pressure switch activated Abnormal low pressure drop Faulty low pressure sensor

Faulty outdoor unit electronic board Faulty connector contact

✔ ✔ ✔ ✔
E5 Inverter compressor motor or overheating Inverter compressor lockup High differential pressure

Faulty Inverter electronic board UVW connection error

Faulty connector contact

 

✔

 

✔

 

✔

✔  

✔

E6 STD compressor motor lockup/overcurrent Faulty compressor

Faulty control electronic board The shutoff valve is not open

✔ ✔ ✔ ✔
E6 Circuit No. 1 – Compressor overcurrent Faulty electronic expansion valve Insufficient refrigerant amount Faulty compressor ✔
 

E7

Malfunction caused by the outdoor unit fan motor circuit Faulty fan motor

Missing or incorrect connection of the wiring harness/connector between the fan motor and the electronic board

Foreign objects blocking the fan are preventing it from operating.

 

✔

 

✔

 

✔

 

✔

 

✔

E8 Inverter compressor overcurrent Faulty compressor

Faulty Inverter main circuit capacitor Faulty outdoor unit electronic board Faulty power transistor

✔ ✔
E9 Malfunction caused by the electronic expansion valve coil Disconnected electronic expansion valve connectors

Faulty electronic expansion valve coil Faulty outdoor unit electronic board

✔ ✔ ✔ ✔
EA Malfunction caused by the four-way valve or cooling/heating switchover Faulty four-way valve Insufficient gas

Faulty outdoor unit electronic board Faulty thermistor

✔
EC Malfunction caused by the inlet water temperature Cooling water temperature abnormality Faulty outdoor unit electronic board Faulty thermistor ✔
F3 Malfunction caused by the discharge pipe temperature Faulty discharge pipe thermistor Abnormal discharge pipe temperature Faulty outdoor unit electronic board Faulty connector contact ✔ ✔ ✔ ✔ ✔
 

F6

Abnormally high pressure or refrigerant overcharge Refrigerant overcharge

Disconnected heat exchanger defrost thermistor

Disconnected outdoor air thermistor

Disconnected liquid pipe temperature thermistor Faulty outdoor unit electronic board

 

✔

 

✔

 

✔

 

✔

H0 Malfunction caused by the compressor sensor circuit Disconnected wiring harness, or connection fault Faulty electronic board ✔ ✔
H1 Malfunction caused by the room temperature sensor or the humidifier unit damper Faulty limit switch Faulty damper ✔ ✔
H3 Malfunction caused by the high-pressure switch Faulty high-pressure switch Broken cable

Faulty outdoor unit electronic board Faulty connector contact

✔ ✔ ✔ ✔ ✔
H4 Malfunction caused by the low-pressure switch Faulty low-pressure switch Broken cable

Faulty outdoor unit electronic board Faulty connector contact

 

✔

 

✔

 

✔

 

Code error code

 

Nature of the malfunction

 

Suspected causes

Units
RA SkyAir VRV Monobloc Heat recovery ventilator (HRV) Chiller unit Fan coil unit
Outdoor unit H5 Malfunction caused by the compressor motor overload thermistor Faulty compressor motor overload thermistor

Faulty connector contact

✔ ✔
H6 Malfunction caused by the position detection sensor Faulty compressor contact or cable Faulty compressor

Faulty outdoor unit electronic board

✔ ✔ ✔
H7 Malfunction caused by the outdoor unit fan motor signal Abnormal signal from the fan motor (circuit failure)

Disconnection/short circuit in the fan motor cables or connector unplugged

Faulty Inverter electronic board

 

✔

 

✔

 

✔

 

✔

H8 Malfunction caused by the compressor input circuit (CT) Faulty power transistor Faulty reactor

Inverter system wiring fault

Faulty outdoor unit electronic board

 

✔

 

✔

H9 Malfunction caused by the outdoor air thermistor Thermistor connection fault

Faulty outdoor unit electronic board Faulty outdoor air thermistor

✔ ✔ ✔ ✔ ✔
C Malfunction caused by the (hot) water temperature thermistor Thermistor connection fault

Faulty outdoor unit electronic board Faulty water temperature thermistor

✔ ✔ ✔
HF Alarm at the thermal storage unit or thermal storage controller Thermal storage unit wiring fault Incorrect setting

Excessive number of thermal storage tanks

✔
HJ Malfunction caused by the water level in the thermal storage tank Low water level

Faulty switch setting Faulty water level sensor Faulty connector contact

 

✔

 

✔

 

✔

 

✔

J1 Malfunction caused by the pressure sensor Faulty contact at the pressure sensor connector

Faulty pressure sensor

Faulty outdoor unit electronic board

 

✔

 

✔

 

✔

✔
J2 Malfunction caused by the compressor current sensor Faulty current sensor Faulty compressor

Faulty outdoor unit electronic board

✔ ✔ ✔ ✔ ✔
J3 Malfunction caused by the discharge pipe thermistor Thermistor connection fault Faulty discharge pipe thermistor Faulty outdoor unit electronic board ✔ ✔ ✔ ✔ ✔
J4 Malfunction caused by the low-pressure equivalent saturation temperature sensor circuit Thermistor connection fault Faulty thermistor

Faulty outdoor unit electronic board

 

✔

 

✔

J5 Malfunction caused by the suction pipe thermistor Thermistor connection fault Faulty suction pipe thermistor Faulty outdoor unit electronic board ✔ ✔ ✔ ✔
J6 Malfunction caused by the heat exchanger thermistor Thermistor connection fault Faulty heat exchanger thermistor Faulty outdoor unit electronic board ✔ ✔ ✔ ✔ ✔
J7 Malfunction caused by the thermistor (refrigerant circuit) Thermistor connection fault Faulty liquid pipe thermistor

Faulty outdoor unit electronic board

✔ ✔ ✔ ✔
J8 Malfunction caused by the thermistor (refrigerant circuit) Thermistor connection fault Faulty liquid pipe thermistor

Faulty outdoor unit electronic board

✔ ✔ ✔ ✔ ✔
J9 Malfunction caused by the thermistor (refrigerant circuit) Thermistor connection fault Faulty gas pipe thermistor

Faulty outdoor unit electronic board

✔ ✔ ✔ ✔ ✔
JA Malfunction caused by the high-pressure sensor Faulty connector contact

Low-pressure sensor incorrectly connected in place of the high-pressure sensor

Faulty high-pressure sensor

Faulty outdoor unit electronic board

 

✔

 

✔

 

✔

 

✔

JC Malfunction caused by the low-pressure sensor Faulty connector contact

High-pressure sensor incorrectly connected in place of the low-pressure sensor

Faulty low-pressure sensor

Faulty outdoor unit electronic board

 

✔

 

✔

 

✔

 

✔

 

Code error code

 

Nature of the malfunction

 

Suspected causes

Units
RA SkyAir VRV Monobloc Heat recovery ventilator (HRV) Chiller unit Fan coil unit
Outdoor unit JE Malfunction caused by the oil pressure sensor

or the sub-tank thermistor

Faulty connector contact

Faulty sub-tank thermistor

Faulty outdoor unit electronic board

 

✔

JF Malfunction caused by the oil level sensor or

the heat exchanger heater thermistor

Faulty connector contact

Faulty heat exchanger thermistor Faulty outdoor unit electronic board

 

✔

L0 Malfunction caused by the Inverter circuit Insufficient power supply Faulty power transistor

Faulty outdoor unit electronic board

✔ ✔
L1 Malfunction caused by the Inverter electronic board Compressor wiring fault

Faulty outdoor unit fan motor Blown fuse

Faulty Inverter electronic board

 

✔

 

✔

 

✔

 

✔

L3 Electrical box temperature rise Rise in fin temperature due to a short circuit Faulty outdoor unit fan motor

Faulty power transistor

Faulty outdoor unit electronic board

 

✔

 

✔

 

✔

 

✔

L4 Malfunction caused by the rise in Inverter radiator fin temperature Rise in fin temperature due to a short circuit

Faulty fin thermistor

✔ ✔ ✔ ✔ ✔
L5 Instantaneous Inverter overcurrent (DC output) Faulty compressor coil (such as a disconnected cable or insulation issue)

Compressor startup failure (mechanical lock) Faulty Inverter electronic board

 

✔

 

✔

 

✔

 

✔

 

✔

L6 Instantaneous Inverter overcurrent (AC output) Refrigerant overcharge

Insufficient power supply Faulty compressor

Faulty Inverter unit

 

✔

 

✔

L8 Malfunction caused by an Inverter compressor overcurrent Compressor overload

Disconnected cable at the compressor coil

Disconnected compressor wiring Faulty Inverter electronic board

 

✔

 

✔

 

✔

 

✔

 

✔

 

L9

Malfunction caused by an Inverter compressor startup error

(stall prevention)

The shutoff valve is not open Faulty compressor

Incorrect cable connection on the compressor High differential pressure before compressor startup

Faulty Inverter electronic board

 

✔

 

✔

 

✔

 

✔

LA Malfunction caused by the power transistor Defective power transistor Defective compressor

Defective Inverter circuit board

✔ ✔
 

LC

Malfunction caused by transmission issues between the control

circuit board and the Inverter board

Faulty connection between the inverter circuit board and the main circuit board

External factors (noise, etc.) Defective Inverter compressor

Fault in the control circuit board (transmission block)

 

✔

 

✔

 

✔

 

✔

 

✔

M1 Malfunction of the central remote control circuit board Fault in the centralized remote control circuit board ✔ ✔ ✔ ✔ ✔
M8 Transmission malfunction between the optional controls and the centralized control Electrical disconnection of another centralized control Activation of the centralized control’s reset switch

Faulty transmission wiring

Change of the centralized remote control’s address

 

✔

 

✔

 

✔

 

✔

 

✔

MA Incorrect combination of the centralized control’s optional controls Incorrect combination of the centralized control’s optional controls

Several master remote controls are connected. Faulty centralized control setting Centralized control fault

 

✔

 

✔

 

✔

 

✔

 

✔

MC Duplicate address, incorrect setting Duplicate address of the centralized remote control ✔ ✔ ✔ ✔ ✔
P0 Insufficient refrigerant level (thermal storage unit) Insufficient refrigerant level Blocked refrigerant piping ✔ ✔
P1 Power supply voltage imbalance or Inverter circuit board issue Open phase

Phase-to-phase voltage imbalance

Defective capacitor in the main circuit Faulty wiring in the main circuit

Defective Inverter circuit board

 

✔

 

✔

 

✔

 

✔