Daikin self-diagnostic by error code
Do you have a Daikin air-to-water heat pump or a Daikin air-to-air heat pump? Find the problem using the error code on Daikin’s self-diagnostic chart
Download the Daikin self-diagnostic chart by error code
Indoor unit
|
Code malfunction |
Nature of the malfunction |
Suspected causes |
Models | |||||||
| RA | SkyAir | VRV | Monobloc | Energy recovery ventilator (HRV) | Chiller unit | Fan coil unit | ||||
| A0 | External protection device activated | The external protection device connected to the T1-T2 terminal block of the indoor unit is activated. | ✔ | ✔ | ✔ | |||||
| A1 | Malfunction caused by the indoor unit’s electronic board | Faulty indoor unit electronic board External factor (noise, etc.) | ✔ | ✔ | ✔ | ✔ | ✔ | ✔ | ||
| A3 | Malfunction caused by the drain level control system | Drain blockage, upward slope, etc. Faulty drain pump
Faulty float switch or short-circuited connector |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
| A4 | Malfunction caused by freeze protection | Insufficient water supply Low water temperature setting
Faulty water temperature thermistor |
✔ | ✔ | ✔ | ✔ | ✔ | ✔ | ||
| A5 | High pressure control in heating mode, freeze protection control in cooling mode | Clogged indoor unit air filter and short circuit Faulty indoor unit heat exchanger thermistor |
✔ |
✔ |
✔ |
✔ |
||||
| A6 | Malfunction caused by the fan motor | Broken wires, short circuit, or disconnected connectors on the fan motor harness Faulty fan motor
Faulty indoor unit electronic board |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
| A7 | Malfunction caused by the swing flap motor | Faulty swing flap motor
Faulty indoor unit electronic board Faulty connection cable Faulty airflow direction adjustment flap cam |
✔ |
✔ |
||||||
| A8 | Malfunction caused by overcurrent at the AC input or power supply | Abnormal supply voltage
Faulty connection on the signal line Faulty wiring |
✔ | ✔ | ✔ | |||||
| A9 | Malfunction caused by the electronic expansion valve | Faulty electronic expansion valve coil Faulty indoor unit electronic board Faulty relay wires | ✔ | ✔ | ✔ | ✔ | ✔ | |||
| AA | Overheating of the heating device | 26WH activation | ✔ | ✔ | ||||||
| AF | Malfunction caused by a humidification system | Leak in the humidifier unit (optional accessory) Faulty drain pipe (upward slope, etc.) Faulty indoor unit electronic board | ✔ | ✔ | ✔ | |||||
| AH | Malfunction caused by the air filter dust collector | Faulty dust collection element Dirty insulation component
Faulty high-voltage power unit Faulty indoor unit electronic board |
✔ |
✔ |
✔ |
✔ |
||||
| AJ | Malfunction caused by the power setting (indoor unit electronic board) | The power setting adapter was not installed when the electronic board was replaced.
Faulty indoor unit electronic board |
✔ | ✔ | ✔ | |||||
| C1 | Transmission failure (between the indoor unit’s
electronic board and the secondary electronic board) |
Faulty connector connection on the indoor unit’s electronic board |
✔ |
✔ |
||||||
| C4 | Malfunction caused by the heat exchanger liquid pipe thermistor | Faulty liquid pipe thermistor Faulty indoor unit electronic board Faulty connector contact | ✔ | ✔ | ✔ | ✔ | ✔ | ✔ | ✔ | |
| C5 | Malfunction caused by the heat exchanger gas pipe thermistor | Faulty gas pipe thermistor
Faulty indoor unit electronic board Faulty connector contact |
✔ | ✔ | ✔ | ✔ | ✔ | |||
| C6 | Malfunction caused by the fan motor sensor or fan control motor | Faulty fan electronic board Faulty power setting adapter connection
On-site setting error |
✔ |
✔ |
||||||
| C7 | Fault in the front panel drive motor | Faulty front panel drive motor Faulty limit switch | ✔ | |||||||
| C9 | Malfunction caused by the intake air thermistor | Faulty intake pipe thermistor Faulty indoor unit electronic board Faulty connector contact | ✔ | ✔ | ✔ | ✔ | ✔ | ✔ | ||
| CA | Malfunction caused by the discharge air thermistor | Faulty discharge air thermistor Faulty indoor unit electronic board Faulty connector contact | ✔ | ✔ | ✔ | ✔ | ||||
| Malfunction caused by the humidity sensor circuit | Faulty humidity sensor Faulty connector contact | ✔ | ✔ | ✔ | ||||||
| CJ | Room temperature thermistor fault in the remote control | Faulty room temperature thermistor in the remote control
Faulty remote control electronic board External factor (noise, etc.) |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
Outdoor unit
|
Code malfunction |
Nature of the malfunction |
Suspected causes |
Models | |||||||
| RA | SkyAir | VRV | Monobloc | Energy recovery ventilator (HRV) | Chiller unit | Fan coil unit | ||||
| Outdoor unit | E0 | Protection devices activated (unified) | The protection device connected to the outdoor unit’s electronic board is activated.
Faulty contact on the protection device connector |
✔ | ✔ | ✔ | ||||
| E1 | Faulty outdoor unit electronic board | Faulty outdoor unit electronic board Faulty connection of indoor/outdoor relay wires | ✔ | ✔ | ✔ | ✔ | ✔ | |||
| E3 | High pressure switch activated | Dirty outdoor unit heat exchanger Faulty high pressure switch
Blocked refrigerant piping Faulty connector contact |
✔ | ✔ | ✔ | ✔ | ||||
| E3 | Circuit No. 1
High pressure switch activated |
Dirty outdoor unit heat exchanger Insufficient water supply
Blocked refrigerant piping Faulty connector contact Faulty high pressure sensor |
✔ | |||||||
| E4 | Low pressure switch activated | Abnormal low pressure drop Faulty low pressure sensor
Faulty outdoor unit electronic board Faulty connector contact |
✔ | ✔ | ✔ | ✔ | ||||
| E5 | Inverter compressor motor or overheating | Inverter compressor lockup High differential pressure
Faulty Inverter electronic board UVW connection error Faulty connector contact |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
| E6 | STD compressor motor lockup/overcurrent | Faulty compressor
Faulty control electronic board The shutoff valve is not open |
✔ | ✔ | ✔ | ✔ | ||||
| E6 | Circuit No. 1 – Compressor overcurrent | Faulty electronic expansion valve Insufficient refrigerant amount Faulty compressor | ✔ | |||||||
|
E7 |
Malfunction caused by the outdoor unit fan motor circuit | Faulty fan motor
Missing or incorrect connection of the wiring harness/connector between the fan motor and the electronic board Foreign objects blocking the fan are preventing it from operating. |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
| E8 | Inverter compressor overcurrent | Faulty compressor
Faulty Inverter main circuit capacitor Faulty outdoor unit electronic board Faulty power transistor |
✔ | ✔ | ||||||
| E9 | Malfunction caused by the electronic expansion valve coil | Disconnected electronic expansion valve connectors
Faulty electronic expansion valve coil Faulty outdoor unit electronic board |
✔ | ✔ | ✔ | ✔ | ||||
| EA | Malfunction caused by the four-way valve or cooling/heating switchover | Faulty four-way valve Insufficient gas
Faulty outdoor unit electronic board Faulty thermistor |
✔ | |||||||
| EC | Malfunction caused by the inlet water temperature | Cooling water temperature abnormality Faulty outdoor unit electronic board Faulty thermistor | ✔ | |||||||
| F3 | Malfunction caused by the discharge pipe temperature | Faulty discharge pipe thermistor Abnormal discharge pipe temperature Faulty outdoor unit electronic board Faulty connector contact | ✔ | ✔ | ✔ | ✔ | ✔ | |||
|
F6 |
Abnormally high pressure or refrigerant overcharge | Refrigerant overcharge
Disconnected heat exchanger defrost thermistor Disconnected outdoor air thermistor Disconnected liquid pipe temperature thermistor Faulty outdoor unit electronic board |
✔ |
✔ |
✔ |
✔ |
||||
| H0 | Malfunction caused by the compressor sensor circuit | Disconnected wiring harness, or connection fault Faulty electronic board | ✔ | ✔ | ||||||
| H1 | Malfunction caused by the room temperature sensor or the humidifier unit damper | Faulty limit switch Faulty damper | ✔ | ✔ | ||||||
| H3 | Malfunction caused by the high-pressure switch | Faulty high-pressure switch Broken cable
Faulty outdoor unit electronic board Faulty connector contact |
✔ | ✔ | ✔ | ✔ | ✔ | |||
| H4 | Malfunction caused by the low-pressure switch | Faulty low-pressure switch Broken cable
Faulty outdoor unit electronic board Faulty connector contact |
✔ |
✔ |
✔ |
|||||
|
Code error code |
Nature of the malfunction |
Suspected causes |
Units | |||||||
| RA | SkyAir | VRV | Monobloc | Heat recovery ventilator (HRV) | Chiller unit | Fan coil unit | ||||
| Outdoor unit | H5 | Malfunction caused by the compressor motor overload thermistor | Faulty compressor motor overload thermistor
Faulty connector contact |
✔ | ✔ | |||||
| H6 | Malfunction caused by the position detection sensor | Faulty compressor contact or cable Faulty compressor
Faulty outdoor unit electronic board |
✔ | ✔ | ✔ | |||||
| H7 | Malfunction caused by the outdoor unit fan motor signal | Abnormal signal from the fan motor (circuit failure)
Disconnection/short circuit in the fan motor cables or connector unplugged Faulty Inverter electronic board |
✔ |
✔ |
✔ |
✔ |
||||
| H8 | Malfunction caused by the compressor input circuit (CT) | Faulty power transistor Faulty reactor
Inverter system wiring fault Faulty outdoor unit electronic board |
✔ |
✔ |
||||||
| H9 | Malfunction caused by the outdoor air thermistor | Thermistor connection fault
Faulty outdoor unit electronic board Faulty outdoor air thermistor |
✔ | ✔ | ✔ | ✔ | ✔ | |||
| C | Malfunction caused by the (hot) water temperature thermistor | Thermistor connection fault
Faulty outdoor unit electronic board Faulty water temperature thermistor |
✔ | ✔ | ✔ | |||||
| HF | Alarm at the thermal storage unit or thermal storage controller | Thermal storage unit wiring fault Incorrect setting
Excessive number of thermal storage tanks |
✔ | |||||||
| HJ | Malfunction caused by the water level in the thermal storage tank | Low water level
Faulty switch setting Faulty water level sensor Faulty connector contact |
✔ |
✔ |
✔ |
✔ |
||||
| J1 | Malfunction caused by the pressure sensor | Faulty contact at the pressure sensor connector
Faulty pressure sensor Faulty outdoor unit electronic board |
✔ |
✔ |
✔ |
✔ | ||||
| J2 | Malfunction caused by the compressor current sensor | Faulty current sensor Faulty compressor
Faulty outdoor unit electronic board |
✔ | ✔ | ✔ | ✔ | ✔ | |||
| J3 | Malfunction caused by the discharge pipe thermistor | Thermistor connection fault Faulty discharge pipe thermistor Faulty outdoor unit electronic board | ✔ | ✔ | ✔ | ✔ | ✔ | |||
| J4 | Malfunction caused by the low-pressure equivalent saturation temperature sensor circuit | Thermistor connection fault Faulty thermistor
Faulty outdoor unit electronic board |
✔ |
✔ |
||||||
| J5 | Malfunction caused by the suction pipe thermistor | Thermistor connection fault Faulty suction pipe thermistor Faulty outdoor unit electronic board | ✔ | ✔ | ✔ | ✔ | ||||
| J6 | Malfunction caused by the heat exchanger thermistor | Thermistor connection fault Faulty heat exchanger thermistor Faulty outdoor unit electronic board | ✔ | ✔ | ✔ | ✔ | ✔ | |||
| J7 | Malfunction caused by the thermistor (refrigerant circuit) | Thermistor connection fault Faulty liquid pipe thermistor
Faulty outdoor unit electronic board |
✔ | ✔ | ✔ | ✔ | ||||
| J8 | Malfunction caused by the thermistor (refrigerant circuit) | Thermistor connection fault Faulty liquid pipe thermistor
Faulty outdoor unit electronic board |
✔ | ✔ | ✔ | ✔ | ✔ | |||
| J9 | Malfunction caused by the thermistor (refrigerant circuit) | Thermistor connection fault Faulty gas pipe thermistor
Faulty outdoor unit electronic board |
✔ | ✔ | ✔ | ✔ | ✔ | |||
| JA | Malfunction caused by the high-pressure sensor | Faulty connector contact
Low-pressure sensor incorrectly connected in place of the high-pressure sensor Faulty high-pressure sensor Faulty outdoor unit electronic board |
✔ |
✔ |
✔ |
✔ |
||||
| JC | Malfunction caused by the low-pressure sensor | Faulty connector contact
High-pressure sensor incorrectly connected in place of the low-pressure sensor Faulty low-pressure sensor Faulty outdoor unit electronic board |
✔ |
✔ |
✔ |
✔ |
||||
|
Code error code |
Nature of the malfunction |
Suspected causes |
Units | |||||||
| RA | SkyAir | VRV | Monobloc | Heat recovery ventilator (HRV) | Chiller unit | Fan coil unit | ||||
| Outdoor unit | JE | Malfunction caused by the oil pressure sensor
or the sub-tank thermistor |
Faulty connector contact
Faulty sub-tank thermistor Faulty outdoor unit electronic board |
✔ |
||||||
| JF | Malfunction caused by the oil level sensor or
the heat exchanger heater thermistor |
Faulty connector contact
Faulty heat exchanger thermistor Faulty outdoor unit electronic board |
✔ |
|||||||
| L0 | Malfunction caused by the Inverter circuit | Insufficient power supply Faulty power transistor
Faulty outdoor unit electronic board |
✔ | ✔ | ||||||
| L1 | Malfunction caused by the Inverter electronic board | Compressor wiring fault
Faulty outdoor unit fan motor Blown fuse Faulty Inverter electronic board |
✔ |
✔ |
✔ |
✔ |
||||
| L3 | Electrical box temperature rise | Rise in fin temperature due to a short circuit Faulty outdoor unit fan motor
Faulty power transistor Faulty outdoor unit electronic board |
✔ |
✔ |
✔ |
✔ |
||||
| L4 | Malfunction caused by the rise in Inverter radiator fin temperature | Rise in fin temperature due to a short circuit
Faulty fin thermistor |
✔ | ✔ | ✔ | ✔ | ✔ | |||
| L5 | Instantaneous Inverter overcurrent (DC output) | Faulty compressor coil (such as a disconnected cable or insulation issue)
Compressor startup failure (mechanical lock) Faulty Inverter electronic board |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
| L6 | Instantaneous Inverter overcurrent (AC output) | Refrigerant overcharge
Insufficient power supply Faulty compressor Faulty Inverter unit |
✔ |
✔ |
||||||
| L8 | Malfunction caused by an Inverter compressor overcurrent | Compressor overload
Disconnected cable at the compressor coil Disconnected compressor wiring Faulty Inverter electronic board |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
|
L9 |
Malfunction caused by an Inverter compressor startup error
(stall prevention) |
The shutoff valve is not open Faulty compressor
Incorrect cable connection on the compressor High differential pressure before compressor startup Faulty Inverter electronic board |
✔ |
✔ |
✔ |
✔ |
||||
| LA | Malfunction caused by the power transistor | Defective power transistor Defective compressor
Defective Inverter circuit board |
✔ | ✔ | ||||||
|
LC |
Malfunction caused by transmission issues between the control
circuit board and the Inverter board |
Faulty connection between the inverter circuit board and the main circuit board
External factors (noise, etc.) Defective Inverter compressor Fault in the control circuit board (transmission block) |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
| M1 | Malfunction of the central remote control circuit board | Fault in the centralized remote control circuit board | ✔ | ✔ | ✔ | ✔ | ✔ | |||
| M8 | Transmission malfunction between the optional controls and the centralized control | Electrical disconnection of another centralized control Activation of the centralized control’s reset switch
Faulty transmission wiring Change of the centralized remote control’s address |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
| MA | Incorrect combination of the centralized control’s optional controls | Incorrect combination of the centralized control’s optional controls
Several master remote controls are connected. Faulty centralized control setting Centralized control fault |
✔ |
✔ |
✔ |
✔ |
✔ |
|||
| MC | Duplicate address, incorrect setting | Duplicate address of the centralized remote control | ✔ | ✔ | ✔ | ✔ | ✔ | |||
| P0 | Insufficient refrigerant level (thermal storage unit) | Insufficient refrigerant level Blocked refrigerant piping | ✔ | ✔ | ||||||
| P1 | Power supply voltage imbalance or Inverter circuit board issue | Open phase
Phase-to-phase voltage imbalance Defective capacitor in the main circuit Faulty wiring in the main circuit Defective Inverter circuit board |
✔ |
✔ |
✔ |
✔ |
||||