Atlantic Alfea Excellia Air-to-Water Heat Pump – List of Error Codes

List of error codes for the Atlantic Alfea Excellia air-to-water heat pump

Download the manual for the Atlantic Alfea Excellia air-to-water heat pump

Before you begin, here are the most common error codes

  • Error code 10 : outdoor sensor fault.
  • Error code 50 : DHW temperature sensor fault.
  • Error code 60 : room sensor 1 fault.
  • Error code 121 : CC1 outlet temperature not reached.
  • Error code 370 : error on the outdoor unit.

If you can’t find the solution to your problem, you can go directly to the Atlantic manufacturer’s website to look up the issue based on your error code.

Faults displayed on the hydraulic module

Before any work, make sure the main power supply is switched off.
When the heat pump is not powered on, frost protection is not guaranteed.

Depending on whether the fault comes from the outdoor unit or the hydraulic module, it may be shown on the digital display or via the LED on the interface boards.
Faults or failures of the hydraulic module are shown on the user interface display.

The display shows the symbol 
Press the   key to get details on the source of the fault.
Once the error is resolved, faults are automatically reset to zero.

Hydraulic module : Faults visible on the digital display.

 

Error code Error label Error location Heat pump operation despite the error
– No connection. The room sensor’s polarity is not correct. No
10 Outdoor sensor. B9 Yes
33 Heat pump outlet temperature sensor error. B21 Yes
44 Heat pump return temperature sensor error. B71 Yes
50 DHW temperature sensor. B3 Yes
60 Room sensor 1. Yes
65 Room sensor 2. Yes
105 Maintenance message. Yes
121 CC1 outlet temperature not reached. Yes
122 CC2 outlet temperature not reached. Yes
127 Anti-legionella temperature not reached. Yes
369 External fault (safety device). No
370 Outdoor unit error

(during a startup phase, see the “Commissioning” section).

see below. No
441 Zone 2 sensor not configured (if 2-circuit kit) BX31; Set parameter 5700 to 2, 4, or 6 No

Hydraulic module : Flashing LED visible on the interface board.

Outdoor unit error number LED display  

Error label

LED 2 (green) LED 1 (red)
11 1 Flash 1 Flash Communication error between the hydraulic module and the outdoor unit.
23 2 Flashes 3 Flashes Connection forbidden (serial connection error).
31 3 Flashes 1 Flash Hydraulic module power supply error.
32 3 Flashes 2 Flashes Communication error between the controller and the user interface.
41 4 Flashes 1 Flash Connection error between the hydraulic module and the outdoor unit.
42 4 Flashes 2 Flashes Hydraulic module heat exchanger temperature sensor error.
61 6 Flashes 1 Flash Outdoor unit power supply error.
62 6 Flashes 2 Flashes Outdoor unit control board error.
63 6 Flashes 3 Flashes Inverter error.
64 6 Flashes 4 Flashes Active filter error.
65 6 Flashes 5 Flashes IPM board error.
67 6 Flashes 7 Flashes Brief power outage to the outdoor unit (protective action).
68 6 Flashes 8 Flashes Outdoor unit magnetic relay error.
71 7 Flashes 1 Flash Discharge temperature sensor error.
72 7 Flashes 2 Flashes Compressor temperature sensor error.
73 7 Flashes 3 Flashes Heat exchanger temperature sensor error (outlet / center).
74 7 Flashes 4 Flashes Outdoor temperature sensor error.
77 7 Flashes 7 Flashes Outdoor unit radiator temperature error.
78 7 Flashes 8 Flashes Expansion valve temperature sensor error.
84 8 Flashes 4 Flashes Compressor current error.
86 8 Flashes 6 Flashes Pressure switch sensor error / Pressure sensor error.
94 9 Flashes 4 Flashes Current sensor error.
95 9 Flashes 5 Flashes Compressor rotor position error detected. Compressor startup error.
97 9 Flashes 7 Flashes Outdoor unit fan 1 error.
98 9 Flashes 8 Flashes Outdoor unit fan 2 error.
A1 10 Flashes 1 Flash Discharge temperature protection.
A3 10 Flashes 3 Flashes Compressor temperature protection.
A4 10 Flashes 4 Flashes Outdoor unit pressure error.
A5 10 Flashes 5 Flashes Abnormal low pressure.
A9 10 Flashes 9 Flashes Overcurrent error.
Continuous flashing

(on for 1 sec / off for 1 sec)

Recovery operation.
– Lit continuously Off Defrosting.

Faults shown on the single-phase outdoor unit

To access the circuit board, the (right) front panel of the outdoor unit must be removed. Faults are coded as LED flashes.

When an error occurs:

  • The “ERROR” LED (2) flashes.
  • Press the “ENTER” button (SW3) once.
  • The “ERROR” LED (2) flashes a number of times depending on the type of error (see table below).

figure 48 – Location of the switches and LED on the single-phase outdoor unit

 

LED display Error label
1 Flash Serial communication feedback error.
2 Flashes Discharge temperature sensor error.
3 Flashes Pressure switch sensor error.
4 Flashes Heat exchanger outlet temperature sensor error.
5 Flashes Intermediate heat exchanger temperature sensor error.
6 Flashes Expansion valve temperature sensor error.
7 Flashes Outdoor temperature sensor error.
8 Flashes Compressor temperature sensor error.
9 Flashes Radiator temperature sensor error.
11 Flashes Discharge temperature protection (permanent shutdown).
12 Flashes Compressor temperature protection (permanent shutdown).
13 Flashes Current sensor error (permanent shutdown).
14 Flashes Compressor rotor position detection error (permanent shutdown).
15 Flashes Compressor startup error (permanent shutdown).
16 Flashes Fan motor 1 error (permanent shutdown).
17 Flashes Fan motor 2 error (permanent shutdown).
18 Flashes Inverter error.
19 Flashes Active filter error.
20 Flashes Abnormal low pressure.
22 Flashes Hydraulic module fault.

Faults shown on the three-phase outdoor unit

To access the circuit board, the (right) front panel of the outdoor unit must be removed. Faults are coded as LED flashes. When an error occurs:

  • The “ERROR” LED (2) flashes.
  • Press the “ENTER” button (SW4) once.
  • The “ERROR” LED (2) flashes several times depending on the type of error (see table below).

LED display Error label
1 Flash Serial communication return error.
2 Flashes Discharge temperature sensor error.
3 Flashes Pressure switch sensor error.
4 Flashes Exchanger outlet temperature sensor error.
5 Flashes Intermediate exchanger temperature sensor error.
6 Flashes Expansion valve temperature sensor error.
7 Flashes Outdoor temperature sensor error.
8 Flashes Compressor temperature sensor error.
9 Flashes Inverter radiator temperature sensor error.
10 Flashes P.F.C. radiator temperature sensor error.
11 Flashes Discharge temperature protection (permanent shutdown).
12 Flashes Compressor temperature protection (permanent shutdown).
13 Flashes Current sensor error (permanent shutdown).
14 Flashes Compressor rotor position detection error (permanent shutdown).
15 Flashes Compressor startup error (permanent shutdown).
16 Flashes Fan motor 1 error (permanent shutdown).
17 Flashes Fan motor 2 error (permanent shutdown).
18 Flashes Inverter error.
19 Flashes P.F.C. error.
20 Flashes Abnormally low pressure.
22 Flashes Hydraulic module malfunction.