List of error codes for the Auer HRC 70 air-to-water heat pump

List of error codes for the air-to-water heat pump – Auer HRC 70

Download the manual for the Auer HRC 70 air-to-water heat pump

Cut the power before starting any troubleshooting

Screen display Nature of the fault Actions to take
AIR PAC

ERR

 

PAC air sensor fault

• check the connection of the PAC air sensor on the PAC board

• check the connector of the PAC air sensor

• check the ohmic value of the sensor

• replace the PAC air sensor

EVAPO

ERR

 

Defrost sensor fault

• check the connection of the defrost sensor on the PAC board

• check the defrost sensor cable

• check the ohmic value of the sensor

• replace the defrost sensor

AMBIANCE

ERR

 

Room sensor fault

• check the connection of the room sensor on the HRC Pilot board

• check the room sensor cable

• check the ohmic value of the sensor

• replace the room sensor

AMBIANCE 1

ERR

 

Room sensor 1 fault

• check the connection of room sensor 1 on the HRC Pilot board

• check the room sensor 1 cable

• check the ohmic value of the sensor

• replace room sensor 1

AMBIANCE 2

ERR

 

Room sensor 2 fault

• check the connection of room sensor 2 on the HRC Pilot board

• check the room sensor 2 cable

• check the ohmic value of the sensor

• replace room sensor 2

 

BUS

ERR

 

Bus connection fault

• check that the PAC is powered on

• check the bus connection on the HRC Pilot board (2 wires) without ground

• check the bus connection on the PAC board (2 wires) with ground

• three-phase PAC connected with 2 phases reversed

• check the phase controller (green and orange lights should be on)

• check the condition of the 4A fuse on the outdoor unit

COMPRES-1

ERR

 

Compressor 1 sensor fault

• check the connection of the compressor 1 sensor on the PAC board

• check the compressor 1 sensor cable

• check the ohmic value of the sensor

• replace the compressor 1 sensor

COMPRES-2

ERR

 

Compressor 2 sensor fault

• check the connection of the compressor 2 sensor on the PAC board

• check the compressor 2 sensor cable

• check the ohmic value of the sensor

• replace the compressor 2 sensor

 

DEBIT

ERR

 

Insufficient water flow or

No flow

• check that the circulator pump is working properly (manual override)

• check for voltage at the circulator pump terminals (qualified personnel only)

• clean the filter valve

• clear any blockage in the circulator pump if needed

• check that the check valve is installed the right way around

DEBIT BAS

ERR

 

Low water flow

• set the circulator pump to speed 3

• clean the filter valve

• check that the length and diameter of the hydraulic network are suitable

• check that the condenser inlet is not clogged

DEBISTAT

ERR

Flow controller malfunction • check the flow controller wiring on the HRC Pilot board

• check that the flow controller paddle is not stuck

• check that the flow controller has not been bypassed

DEGI. FREQU.

ERR

 

Defrost cycles too frequent

• check that the fan is working properly

• check the condition of the coil

• check that the PAC air sensor and Evapo sensor are working properly

• evaporation pressure too low: (qualified personnel only)

DEGI. LONG

ERR

 

Defrost cycle too long

• check that the fan is working properly

• check the condition of the coil

• check that the PAC air sensor and Evapo sensor are working properly

• check that the four-way valve is working properly: (qualified personnel only)

EXTERIEUR

ERR

 

Outdoor sensor fault

• check the connection of the outdoor sensor on the HRC Pilot board

• check the outdoor sensor cable

• check the ohmic value of the sensor

• replace the outdoor sensor

HORLOGE

ERR

 

Clock failure

•1- Press the clock button and set the date and time

•2- If the fault persists: replace the HRC Pilot’s electronic board

MEMOIRE

ERR

 

Memory card fault

 

• replace the HRC Pilot’s electronic board

MODULE

96°C

Heating water outlet overheat fault > 80°C

Display of the measured temperature

• check that the power relays for the electric backup heaters are working properly

• check that the backup boiler’s flow is sufficient

• check the condition of the backup boiler control

• check that the heating circulator pump is working properly

MODULE

ERR

 

HRC Pilot water outlet sensor fault

• check the connection of the HRC Pilot water outlet sensor on the HRC Pilot board

• check the HRC Pilot water outlet sensor cable

• check the ohmic value of the HRC Pilot water outlet sensor

• replace the HRC Pilot water outlet sensor

 

 

 

Screen display Nature of the fault Actions to take
PAC DEPAR.

76.2°C

PAC outlet overheat fault > 75°C Display of the measured temperature • check the condition of the filter valve: clean the filter

• check that the PAC circulator pump’s flow is sufficient

• check that the heating circulator pump is working properly

PAC DEPAR.

ERR

 

PAC water outlet sensor fault

• check the connection of the PAC water outlet sensor on the PAC board

• check the PAC water outlet sensor cable

• check the ohmic value of the PAC water outlet sensor

• replace the PAC water outlet sensor

PAC RETOU.

ERR

 

PAC water inlet sensor fault

• check the connection of the PAC water inlet sensor on the PAC board

• check the PAC water inlet sensor cable

• check the ohmic value of the PAC water inlet sensor

• replace the PAC water inlet sensor

PB T. DEGIV

ERR

 

Inconsistent evaporator sensor reading

• check that the PAC air sensor and Evapo sensor are working properly

• check that the four-way valve is working properly

• check that the compressor starter is not faulty

• check that the Evapo sensor is not covered in ice

 

PB ALIM CP1

 

Compressor 1 power supply fault

• check that the electrical network is suitable for the heat pump’s power rating

• check that the supply voltage does not drop below 200 W during startup

• check that the compressor 1 starter is not faulty (see “Compressor startup fault” section)

• check the supply voltage

• check the power wiring in the electrical cabinet up to the compressor 1 terminals

• check the compressor 1 discharge sensor

 

PB ALIM CP2

 

Compressor 2 power supply fault

• check that the electrical network is suitable for the heat pump’s power rating

• check that the supply voltage does not drop below 200 W during startup

• check that the compressor 2 starter is not faulty (see “Compressor startup fault” section)

• check the supply voltage

• check the power wiring in the electrical cabinet up to the compressor 2 terminals

• check the compressor 2 discharge sensor

 

STARTER 1

ERR

 

Soft starter 1 fault

• check that the electrical network is suitable for the heat pump’s power rating

• check that the supply voltage does not drop below 200V during startup

• record the starter’s fault code

• check the supply voltage

• check the power wiring in the electrical cabinet up to the compressor 1 terminals

 

STARTER 2

ERR

 

Soft starter 2 fault

• check that the electrical network is suitable for the heat pump’s power rating

• check that the supply voltage does not drop below 200V during startup

• record the starter’s fault code

• check the supply voltage

• check the power wiring in the electrical cabinet up to the compressor 2 terminals

PISCINE

ERR

 

Pool sensor fault

• check the connection of the pool sensor on the HRC Pilot board

• check the pool sensor cable

• check the ohmic value of the pool sensor

• replace the pool sensor

 

PLACE SE

ERR

Outdoor temperature reading fault

 

The outdoor sensor and the PAC air sensor show very different values

• check the position of the outdoor sensor

• check the respective values of both sensors (outdoor and PAC air)

ĺ if one of the two sensors shows an incorrect value, check the condition of that sensor

• check the condition of the cable and connections for each sensor

• replace the faulty sensor

 

PRESSION

0.2

 

Low water pressure fault

• the water pressure in the heating circuit must be above 0.5 bar when cold

• check the tightness of the heating circuit and repair any water leaks

• bleed the air from the high points and from the HRC Pilot

• check that the pressure relief valve in the heat pump is sealed properly

• check that the pressure relief valve in the HRC Pilot is sealed properly

• check that the expansion tank is large enough for the volume of the system

 

SECU. BP

 

PAC low pressure fault

• check that the fan is working properly (capacitor and electrical connections)

• check the surface condition of the finned coil and remove anything that could block airflow through the rear grille (leaves, or other debris…)

• if fully iced over, stop the PAC and let it thaw, pouring warm water over it if needed

• refrigerant leak or blocked defrost valve or faulty expansion valve: the refrigerant circuit must be serviced by a qualified technician

 

SECU. HP 1

 

PAC compressor 1 high pressure fault

• check the condition of the filter valve

• check that the heating network has been properly bled

• check that the PAC circulator pump is working properly

• clean the plate heat exchanger inlet

• malfunction of the discharge valve or four-way valve

 

SECU. HP 2

 

PAC compressor 2 high pressure fault

• check the condition of the filter valve

• check that the heating network has been properly bled

• check that the PAC circulator pump is working properly

• clean the plate heat exchanger inlet

• malfunction of the discharge valve or four-way valve

SONDE ECS

ERR

 

Pool sensor fault

• check the DHW sensor connection on the HRC Pilot board

• check the DHW sensor cable

• check the DHW sensor’s ohmic value

• replace the DHW sensor

 

Faults are indicated by a flashing backlight.

Any fault that blocks operation is signaled by an alarm buzzer. When the fault must be cleared by manual reset, the symbol 🔧 (or similar) is displayed.

 

Display Name Cause of fault Consequence(s) Repair

Clearing the fault

AIR PAC

ERR

Tair sensor failure  

Heat pump Tair sensor out of measurement range

Setpoint temperature = (Max. water temp. + Min. water temp.) / 2 Automatic after repair
 

AMBIANCE 1

ERR

 

Amb1 sensor failure

Note : the room sensor

with display is identified as SONDE INT for circuit 1 only

• The room control for circuit 1 is set to SENSOR and it is out of measurement range

or

• It is not, so the pool sensor is recognized and it is out of measurement range

 

Room in demand

 

Automatic after repair

 

AMBIANCE 2

ERR

 

Amb2 sensor failure

Note: the room sensor with display is identified as SONDE INT for circuit 1 only

Circuit 2 is set to radiators or underfloor heating with a room sensor, and this sensor is out of

measurement range

 

Room in demand

 

Automatic after repair

 

BUS

err

 

BUS

Shielded 2-wire link

or faulty BUS wiring or blown fuse

or faulty board(s)

 

Heat pump stopped,

backup heater only allowed

BUS connection

or fuse replacement

or board(s) replacement /

Manual

 

compres-1

err

Compressor 1 sensor failure Compressor 1 sensor out of measurement range Both compressors stopped

and fan stopped

Automatic after repair
 

Compressor 1 temperature fault

“Compressor 1 overheat” (compressor temperature >115°C) repeated more than 24 times in 24h  

Both compressors stopped

 

Manual

 

compres-2

err

 

Compressor 2 sensor failure

 

Compressor 2 sensor out of measurement range

 

Both compressors stopped

and fan stopped

 

Automatic after repair

 

Compressor 2 temperature fault

“Compressor 2 overheat” (compressor temperature >115°C) repeated more than 24 times in 24h  

Both compressors stopped

 

Manual

DEBIT

ERR

 

Zero flow fault

“Zero flow error” repeated after 8 attempts Heat pump stopped Manual
DEBIT BAS Low flow error Heat pump inlet/outlet temperature difference too high  

Operation unchanged

Manual
 

debitstat

err

 

Flow switch failure

Flow input = 1 and

Heat pump circulator output = 0

Heat pump will not start

= heat pump stopped and backup heater running (if allowed)

 

Automatic as soon as flow = 0 and CPAC = 0

 

Zero flow error

 

Flow input = 0, heat pump circulator = 1

 

Heat pump will not start

Automatic via heat pump circulator attempts

= 1 every 2 minutes

DEGI. FREQU.

ERR

Defrost too frequent fault  

More than 3 defrost cycles per hour

Heat pump stopped,

backup heater only allowed

 

Manual

 

DEGI. LONG

ERR

Defrost too long fault “Defrost too long error” repeated more than 8 times in 24h Heat pump stopped,

backup heater only allowed

Manual
 

Defrost too long error

 

After 20 min. Defrost temp < 15°C

 

Operation unchanged

 

Automatic

 

 

Display Name Cause of fault Consequence(s) Repair

Clearing the fault

EVAPO

ERR

Tdefrost sensor failure  

Tdefrost sensor out of measurement range

Heat pump stopped,

backup heater only allowed

Automatic after repair
exterieur

err

 

Outdoor sensor failure

 

Outdoor sensor out of measurement range

Heat pump air temperature replaces outdoor temperature if outdoor sensor is unplugged  

Automatic after repair

horloge

err

 

Clock

 

•1-Clock not set

• 2-Faulty board

Operation in Permanent eco mode

(comfort schedules ignored)

 

Manual

memory

err

 

Memory

 

Memory fault

PAC shutdown

and backup heater shutdown

Board replacement /

Manual

 

MODULE

96°C

HRC Pilot outlet overheat fault “HRC Pilot outlet overheat error” repeated more than 12 times per 24h Shutdown of both compressors and backup heaters Manual
 

HRC Pilot outlet overheat error

 

TsEAU > 80°C

Temporary shutdown

of one compressor and backup heaters

 

Automatic once TsEAU < 80 – 10°C

PAC OUTLET

ERR

TsPAC sensor failure  

TsPAC sensor out of measurement range

PAC shutdown,

backup heater only allowed

Automatic after repair
 

PAC OUTLET

76.2°C

PAC outlet overheat fault “PAC outlet overheat error” repeated more than 10 times per 24h Shutdown of both compressors and backup heaters Manual
PAC outlet water overheat error  

TsPAC > 75°C

Temporary shutdown of

both compressors and backup heaters

Automatic once TsPAC < 75 – 10°C
PAC RETURN

ERR

TePAC sensor failure  

TePAC sensor out of measurement range

PAC shutdown,

backup heater only allowed

Automatic after repair
 

PB POWER CP1

 

Compressor 1 power supply fault

Problem during startup, unsuitable electrical network, insufficient supply voltage, faulty soft starter. Compressor 1 is shut down.

The heat pump will retry starting the compressor every hour.

 

Manual

once normal operation is restored

 

PB POWER CP2

 

Compressor 2 power supply fault

Problem during startup, unsuitable electrical network, insufficient supply voltage, faulty soft starter. Compressor 2 is shut down.

The heat pump will retry starting the compressor every hour.

 

Manual

once normal operation is restored

 

STARTER 1

ERR

 

Soft starter 1 fault

Problem during startup, unsuitable electrical network, insufficient supply voltage, faulty soft starter. Compressor 1 is shut down.

The heat pump will retry starting the compressor every 20 minutes

 

Manual

 

STARTER 2

ERR

 

Soft starter 2 fault

Problem during startup, unsuitable electrical network, insufficient supply voltage, faulty soft starter. Compressor 2 is shut down.

The heat pump will retry starting the compressor every 20 minutes

 

Manual

 

PB T.DEFROST

 

Inconsistent evaporator sensor

The values read by the air and evaporator sensors are inconsistent while a compressor is running.  

Fault displayed, the heat pump keeps running

Manual

once normal operation is restored

Pilot

err

TsEAU sensor failure  

TsEAU sensor out of measurement range

Backup heater shutdown Automatic after repair
pool

err

Pool sensor failure The pool sensor’s resistance value is too low Pool set to no demand Automatic after repair
SENSOR LOC

ERR

 

Outdoor sensor location error

Tair – Ext > 15K or

Ext – Tair > 15K

 

Temperature for the water curve

= (Tair+Ext)/2

 

Automatic

pressure

err

Pressure sensor failure Pressure sensor disconnected or faulty PAC and backup heater shutdown Automatic after repair

 

 

Display Name Cause of the fault Consequence(s) Repair

fault clearing

pressure

0.2

 

Low water pressure

 

Pressure measured by pressure sensor < 0.3 bar

Shutdown of both compressors and backup heaters

and

of the circulator pumps after 2 min.

 

Automatic once pressure > 0.5 bar

SECU. HP1 HP1 safety HP1 pressure switch opened Shutdown of both compressors Manual
SAFETY HP2 HP2 safety trip Opening of the HP2 pressure switch Shutdown of both compressors Manual
 

SAFETY LP

 

LP low pressure fault

 

Opening of the LP pressure switch

 

Shutdown of both compressors

Automatic when the pressure switch closes Manual after the 3rd error within the same hour
DHW SENSOR

ERR

DHW sensor failure

(Amb2 input on the board)

Circuit 2 is set to domestic hot water with a DHW sensor, and this sensor is out of measurement range.  

DHW set to no demand

Automatic after repair