List of error codes for the Atlantic Takao M2 Muraux R32 air-to-air heat pump
List of error codes for the Atlantic Takao M2 Muraux R32 air-to-air heat pump

Before we begin, here are the most common error codes
- Error code 10 : outdoor sensor fault.
- Error code 50 : DHW temperature sensor fault.
- Error code 60 : room sensor 1 fault.
- Error code 121 : CC1 flow temperature not reached.
- Error code 370 : error on the outdoor unit.
If you can’t find a solution to your problem, you can go directly to the Atlantic manufacturer’s website to look up the issue based on your error code.
Download the manual for the Atlantic Takao M2 Muraux R32 air-to-air heat pump (coming soon)
For the following references:
- ASYG 07 KM
- ASYG 09 KM
- ASYG 12 KM
- ASYG 14 KM
Errors that may occur on the air conditioner can be identified by the state (off, on, blinking) of the “TIMER”, “OPERATION”, and “ECONOMY” indicator lights on the indoor unit.
If you’re using an infrared remote control, error codes will be displayed via the lights near the infrared sensor, through a sequence of blinks. An error code only appears while the unit is running.
If you’re using a wired remote control, error codes will be shown on the remote’s screen. The table below shows the blinking sequences and the error codes. An error display only appears while the unit is running.

- 5s ON / 0.5s OFF
- : 0.1s ON / 0.1s OFF
() : number of blinks.
Turn off the power before proceeding with troubleshooting
| Error display | Remote control
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
| ●(1) | ●(1) | ◊ | 11 | Serial communication error |
|
●(1) |
●(2) |
◊ |
12 |
Remote control communication error
Wired Server room controller communication error |
| ●(1) | ●(5) | ◊ | 15 | Incomplete control measurement |
| ●(1) | ●(6) | ◊ | 16 | Peripheral unit transmission PCB connection error |
| ●(1) | ●(8) | ◊ | 18 | External communication error |
|
●(2) |
●(1) |
◊ |
21 |
Address setting error for the unit or refrigerant circuit number [Simultaneous Multi] |
| ●(2) | ●(2) | ◊ | 22 | Indoor unit capacity error |
| ●(2) | ●(3) | ◊ | 23 | Combination error |
|
●(2) |
●(4) |
◊ |
24 |
• Connection unit number error (indoor slave unit) [Simultaneous Multi]
• Connection unit number error (indoor unit or branch unit) [Simultaneous Multi] |
| ●(2) | ●(6) | ◊ | 26 | Address setting error in the wired remote control system |
| ●(2) | ●(7) | ◊ | 27 | Master unit, slave unit
setting error [Simultaneous Multi] |
| ●(2) | ●(9) | ◊ | 29 | Connected unit number error in the
wired remote control setup |
| ●(3) | ●(1) | ◊ | 31 | Power interruption error |
| ●(3) | ●(2) | ◊ | 32 | Indoor unit PCB model information error |
| ●(3) | ●(3) | 33 | Indoor unit motor power consumption detection error | |
| ●(3) | ●(5) | ◊ | 35 | Manual auto switch error |
| ●(3) | ●(9) | ◊ | 39 | Indoor unit fan motor power supply error |
| ●(3) | ●(10) | ◊ | 3A | Indoor unit / wired remote control
communication circuit error |
| ●(4) | ●(1) | ◊ | 41 | Room temperature sensor error |
|
●(4) |
●(2) |
◊ |
42 |
Outdoor unit heat exchanger average temperature sensor error |
| ●(4) | ●(4) | ◊ | 44 | Occupancy sensor error |
| Error display | Remote control
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
| ●(5) | ●(1) | ◊ | 51 | Indoor unit fan motor 1 error (Main fan) |
| ●(5) | ●(3) | ◊ | 53 | Drain pump error |
| ●(5) | ●(4) | ◊ | 54 | Electric air purifier reverse VDD error |
| ●(5) | ●(5) | ◊ | 55 | Filter setting error |
| ●(5) | ●(7) | ◊ | 57 | Damper error |
| ●(5) | ●(8) | ◊ | 58 | Air inlet grille error |
| ●(5) | ●(9) | ◊ | 59 | Indoor unit fan motor 2 error (Left side fan) |
| ●(5) | ●(10) | ◊ | 5A | Indoor unit fan motor 3 error (Right side fan) |
| ●(5) | ●(15) | ◊ | 5U | Indoor unit error |
| ●(6) | ●(1) | 61 | Wiring error, reversed or missing phases
on the indoor unit |
|
|
●(6) |
●(2) |
◊ |
62 |
Outdoor unit main PCB model information error or communication error |
| ●(6) | ●(3) | ◊ | 63 | Inverter error |
| ●(6) | ●(4) | ◊ | 64 | Active filter error and PFC error |
| ●(6) | ●(5) | ◊ | 65 | L terminal trip error |
|
●(6) |
●(8) |
◊ |
68 |
Outdoor unit current limiting resistor temperature rise error |
| ●(6) | ●(10) | ◊ | 6A | Display PCB microcomputer communication error |
| ●(7) | ●(1) | ◊ | 71 | Discharge temperature sensor error |
| ●(7) | ●(2) | ◊ | 72 | Compressor temperature sensor error |
|
●(7) |
●(3) |
◊ |
73 |
Indoor unit heat exchanger liquid temperature sensor error |
| ●(7) | ●(4) | ◊ | 74 | Outdoor temperature sensor error |
| ●(7) | ●(5) | ◊ | 75 | Suction gas temperature sensor error |
|
●(7) |
●(6) |
◊ |
76 |
• 2-way valve temperature sensor error
• 3-way valve temperature sensor error |
| ●(7) | ●(7) | ◊ | 77 | Cold source temperature sensor error |
| Error display | Remote control
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
|
●(8) |
●(2) |
◊ |
82 |
• Subcooling heat exchanger gas inlet temperature sensor error
• Subcooling heat exchanger gas outlet temperature sensor error |
| ●(8) | ●(3) | ◊ | 83 | Liquid pipe temperature sensor error |
| ●(8) | ●(4) | ◊ | 84 | Current sensor error |
|
●(8) |
●(6) |
◊ |
86 |
• Discharge pressure sensor error
• Suction pressure sensor error • High pressure switch error |
| ●(9) | ●(4) | ◊ | 94 | Trip detection |
| ●(9) | ●(5) | ◊ | 95 | Compressor rotor position detection error |
| ●(9) | ●(7) | ◊ | 97 | Outdoor unit fan motor error |
| ●(9) | ●(8) | ◊ | 98 | Outdoor unit fan motor 2 error |
| ●(9) | ●(9) | ◊ | 99 | 4-way valve error |
| ●(9) | ●(10) | ◊ | 9A | Expansion valve coil error |
| ●(10) | ●(1) | ◊ | A1 | Discharge temperature error |
| ●(10) | ●(3) | ◊ | A3 | Compressor temperature error |
| ●(10) | ●(4) | ◊ | A4 | High pressure error |
| ●(10) | ●(5) | ◊ | A5 | Low pressure error |
| ●(13) | ●(2) | ◊ | J2 | Branch box errors
[Flexible Multi] |
Points to check
Indoor unit
- Normal operation of all the remote control buttons.
- Normal operation of the “OPERATION,” “TIMER,” and “ECONOMY” indicator lights.
- Normal operation of the air deflection louvers.
- Normal condensate water drainage (if needed, slowly pour a little water into the unit’s heat exchanger with a squeeze bottle to check proper drainage).
- Check that there is no abnormal noise or vibration in Outdoor unit
- Check that there is no abnormal noise or vibration in
- Check that neither noise, airflow, nor water or ice coming from the outdoor unit causes any
- Also check that there is no leakage of
Do not leave the air conditioner running in “test” mode for too long. For the operating procedure, refer to the user manual
| Error display | Remote control
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
| ●(1) | ●(1) | ◊ | 11 | Serial communication error |
|
●(1) |
●(2) |
◊ |
12 |
Remote control communication error
Wired Server room controller communication error |
| ●(1) | ●(5) | ◊ | 15 | Incomplete check measurement |
| ●(1) | ●(6) | ◊ | 16 | Peripheral unit transmission PCB connection error |
| ●(1) | ●(8) | ◊ | 18 | External communication error |
|
●(2) |
●(1) |
◊ |
21 |
Address setting error for the unit or refrigerant circuit number [Simultaneous Multi] |
| ●(2) | ●(2) | ◊ | 22 | Indoor unit capacity error |
| ●(2) | ●(3) | ◊ | 23 | Combination error |
|
●(2) |
●(4) |
◊ |
24 |
• Connection unit number error (indoor slave unit) [Simultaneous Multi]
• Connection unit number error (indoor unit or branch unit) [Simultaneous Multi] |
| ●(2) | ●(6) | ◊ | 26 | Address setting error in the wired remote control system |
| ●(2) | ●(7) | ◊ | 27 | Master unit, slave unit setting error [Simultaneous Multi] |
| ●(2) | ●(9) | ◊ | 29 | Connected unit number error in the wired remote control configuration |
| ●(3) | ●(1) | ◊ | 31 | Power supply interruption error |
| ●(3) | ●(2) | ◊ | 32 | Indoor unit PCB model information error |
| ●(3) | ●(3) | 33 | Indoor unit motor power consumption detection error | |
| ●(3) | ●(5) | ◊ | 35 | Manual/auto switch error |
| ●(3) | ●(9) | ◊ | 39 | Indoor unit fan motor power supply error |
| ●(3) | ●(10) | ◊ | 3A | Indoor unit / wired remote control communication circuit error |
| ●(4) | ●(1) | ◊ | 41 | Room temperature sensor error |
|
●(4) |
●(2) |
◊ |
42 |
Outdoor unit heat exchanger average temperature sensor error |
| ●(4) | ●(4) | ◊ | 44 | Occupancy sensor error |
| Error display | Remote control
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
| ●(5) | ●(1) | ◊ | 51 | Indoor unit fan motor 1 error (main fan) |
| ●(5) | ●(3) | ◊ | 53 | Drain pump error |
| ●(5) | ●(4) | ◊ | 54 | Electric air purifier reverse VDD error |
| ●(5) | ●(5) | ◊ | 55 | Filter setting error |
| ●(5) | ●(7) | ◊ | 57 | Damper error |
| ●(5) | ●(8) | ◊ | 58 | Air intake grille error |
| ●(5) | ●(9) | ◊ | 59 | Indoor unit fan motor 2 error (left-side fan) |
| ●(5) | ●(10) | ◊ | 5A | Indoor unit fan motor 3 error (right-side fan) |
| ●(5) | ●(15) | ◊ | 5U | Indoor unit error |
| ●(6) | ●(1) | 61 | Indoor unit wiring error, reversed or missing phases | |
|
●(6) |
●(2) |
◊ |
62 |
Outdoor unit main PCB model information error or communication error |
| ●(6) | ●(3) | ◊ | 63 | Inverter error |
| ●(6) | ●(4) | ◊ | 64 | Active filter error and PFC error |
| ●(6) | ●(5) | ◊ | 65 | L terminal tripping error |
|
●(6) |
●(8) |
◊ |
68 |
Outdoor unit current limiting resistor temperature rise error |
| ●(6) | ●(10) | ◊ | 6A | Display PCB microcomputer communication error |
| ●(7) | ●(1) | ◊ | 71 | Discharge temperature sensor error |
| ●(7) | ●(2) | ◊ | 72 | Compressor temperature sensor error |
|
●(7) |
●(3) |
◊ |
73 |
Indoor unit heat exchanger liquid temperature sensor error |
| ●(7) | ●(4) | ◊ | 74 | Outdoor temperature sensor error |
| ●(7) | ●(5) | ◊ | 75 | Suction gas temperature sensor error |
|
●(7) |
●(6) |
◊ |
76 |
• 2-way valve temperature sensor error
• 3-way valve temperature sensor error |
| ●(7) | ●(7) | ◊ | 77 | Cold source temperature sensor error |
| Error display | Remote control
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
|
●(8) |
●(2) |
◊ |
82 |
• Subcooling heat exchanger gas inlet temperature sensor error
• Subcooling heat exchanger gas outlet temperature sensor error |
| ●(8) | ●(3) | ◊ | 83 | Liquid pipe temperature sensor error |
| ●(8) | ●(4) | ◊ | 84 | Current sensor error |
|
●(8) |
●(6) |
◊ |
86 |
• Discharge pressure sensor error
• Suction pressure sensor error • High pressure switch error |
| ●(9) | ●(4) | ◊ | 94 | Trip detection |
| ●(9) | ●(5) | ◊ | 95 | Compressor rotor position detection error |
| ●(9) | ●(7) | ◊ | 97 | Outdoor unit fan motor error |
| ●(9) | ●(8) | ◊ | 98 | Outdoor unit fan motor 2 error |
| ●(9) | ●(9) | ◊ | 99 | 4-way valve error |
| ●(9) | ●(10) | ◊ | 9A | Expansion valve coil error |
| ●(10) | ●(1) | ◊ | A1 | Discharge temperature error |
| ●(10) | ●(3) | ◊ | A3 | Compressor temperature error |
| ●(10) | ●(4) | ◊ | A4 | High pressure error |
| ●(10) | ●(5) | ◊ | A5 | Low pressure error |
| ●(13) | ●(2) | ◊ | J2 | Branch box error [Multi Flexible] |
Points to check
Indoor unit
- Normal operation of all the remote control buttons.
- Normal operation of the “OPERATION,” “TIMER,” and “ECONOMY” indicator lights.
- Normal operation of the air deflection louvers.
- Normal condensate water drainage (if needed, slowly pour a little water into the unit’s heat exchanger with a squeeze bottle to check proper drainage).
- Check that there is no abnormal noise or vibration in Outdoor unit
- Check that there is no abnormal noise or vibration in
- Check that neither noise, airflow, nor water or ice coming from the outdoor unit causes any
- Also check that there is no leakage of
Do not leave the air conditioner running in “test” mode for too long. For the operating procedure, refer to the user manual
| Error display | Remote control
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
| ●(1) | ●(1) | ◊ | 11 | Serial communication error |
|
●(1) |
●(2) |
◊ |
12 |
Remote controller communication error
Wired Server room controller communication error |
| ●(1) | ●(5) | ◊ | 15 | Incomplete control measurement |
| ●(1) | ●(6) | ◊ | 16 | Peripheral unit transmission PCB connection error |
| ●(1) | ●(8) | ◊ | 18 | External communication error |
|
●(2) |
●(1) |
◊ |
21 |
Unit or refrigerant circuit address setting error [Simultaneous Multi] |
| ●(2) | ●(2) | ◊ | 22 | Indoor unit capacity error |
| ●(2) | ●(3) | ◊ | 23 | Combination error |
|
●(2) |
●(4) |
◊ |
24 |
• Connection unit number error (indoor slave unit) [Simultaneous Multi]
• Connection unit number error (indoor unit or branch unit) [Simultaneous Multi] |
| ●(2) | ●(6) | ◊ | 26 | Wired remote controller system address setting error |
| ●(2) | ●(7) | ◊ | 27 | Master unit, slave unit setting error
[Simultaneous Multi] |
| ●(2) | ●(9) | ◊ | 29 | Connected unit number error in the wired
remote controller configuration |
| ●(3) | ●(1) | ◊ | 31 | Power interruption error |
| ●(3) | ●(2) | ◊ | 32 | Indoor unit PCB model information error |
| ●(3) | ●(3) | 33 | Indoor unit motor power consumption detection error | |
| ●(3) | ●(5) | ◊ | 35 | Manual auto switch error |
| ●(3) | ●(9) | ◊ | 39 | Indoor unit fan motor power supply error |
| ●(3) | ●(10) | ◊ | 3A | Indoor unit / wired remote controller
communication circuit error |
| ●(4) | ●(1) | ◊ | 41 | Room temperature sensor error |
|
●(4) |
●(2) |
◊ |
42 |
Outdoor unit heat exchanger average temperature sensor error |
| ●(4) | ●(4) | ◊ | 44 | Occupancy sensor error |
| Error display | Remote controller
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
| ●(5) | ●(1) | ◊ | 51 | Indoor unit fan motor 1 error (Main fan) |
| ●(5) | ●(3) | ◊ | 53 | Drain pump error |
| ●(5) | ●(4) | ◊ | 54 | Electric air purifier reverse VDD error |
| ●(5) | ●(5) | ◊ | 55 | Filter setting error |
| ●(5) | ●(7) | ◊ | 57 | Damper error |
| ●(5) | ●(8) | ◊ | 58 | Air intake grille error |
| ●(5) | ●(9) | ◊ | 59 | Indoor unit fan motor 2 error (Left side fan) |
| ●(5) | ●(10) | ◊ | 5A | Indoor unit fan motor 3 error (Right side fan) |
| ●(5) | ●(15) | ◊ | 5U | Indoor unit error |
| ●(6) | ●(1) | 61 | Indoor unit wiring error, reversed or missing phases | |
|
●(6) |
●(2) |
◊ |
62 |
Outdoor unit main PCB model information error or communication error |
| ●(6) | ●(3) | ◊ | 63 | Inverter error |
| ●(6) | ●(4) | ◊ | 64 | Active filter error and PFC error |
| ●(6) | ●(5) | ◊ | 65 | L terminal trip error |
|
●(6) |
●(8) |
◊ |
68 |
Outdoor unit current limiting resistor temperature rise error |
| ●(6) | ●(10) | ◊ | 6A | Display PCB microcomputer communication error |
| ●(7) | ●(1) | ◊ | 71 | Discharge temperature sensor error |
| ●(7) | ●(2) | ◊ | 72 | Compressor temperature sensor error |
|
●(7) |
●(3) |
◊ |
73 |
Indoor unit heat exchanger liquid temperature sensor error |
| ●(7) | ●(4) | ◊ | 74 | Outdoor temperature sensor error |
| ●(7) | ●(5) | ◊ | 75 | Suction gas temperature sensor error |
|
●(7) |
●(6) |
◊ |
76 |
• 2-way valve temperature sensor error
• 3-way valve temperature sensor error |
| ●(7) | ●(7) | ◊ | 77 | Cold source temperature sensor error |
| Error display | Remote controller
Wired code error |
Description |
||
| Operation (green) | Timer (orange) | Economy (green) | ||
|
●(8) |
●(2) |
◊ |
82 |
• Subcooling heat exchanger gas inlet temperature sensor error
• Subcooling heat exchanger gas outlet temperature sensor error |
| ●(8) | ●(3) | ◊ | 83 | Liquid pipe temperature sensor error |
| ●(8) | ●(4) | ◊ | 84 | Current sensor error |
|
●(8) |
●(6) |
◊ |
86 |
• Discharge pressure sensor error
• Suction pressure sensor error • High pressure switch error |
| ●(9) | ●(4) | ◊ | 94 | Trip detection |
| ●(9) | ●(5) | ◊ | 95 | Compressor rotor position detection error |
| ●(9) | ●(7) | ◊ | 97 | Outdoor unit fan motor error |
| ●(9) | ●(8) | ◊ | 98 | Outdoor unit fan motor 2 error |
| ●(9) | ●(9) | ◊ | 99 | 4-way valve error |
| ●(9) | ●(10) | ◊ | 9A | Expansion valve coil error |
| ●(10) | ●(1) | ◊ | A1 | Discharge temperature error |
| ●(10) | ●(3) | ◊ | A3 | Compressor temperature error |
| ●(10) | ●(4) | ◊ | A4 | High pressure error |
| ●(10) | ●(5) | ◊ | A5 | Low pressure error |
| ●(13) | ●(2) | ◊ | J2 | Branch box errors
[Flexible Multi] |
Points to check
Indoor unit
- Normal operation of all remote controller buttons.
- Normal operation of the “OPERATION,” “TIMER,” and “ECONOMY” indicator lights.
- Normal operation of the air deflection louvers.
- Normal condensate drainage (if needed, gently pour a little water into the unit’s heat exchanger with a squeeze bottle to check that it drains properly).
- Check that there is no abnormal noise or vibration when Outdoor unit
- Check that there is no abnormal noise or vibration when
- Check that neither noise, airflow, nor water or ice coming out of the outdoor unit causes any inconvenience to the
- Check once more that there is no leakage of
Do not let the air conditioner run in “test” mode for too long. For the operating procedure, refer to the user manual