List of error codes for the De Dietrich HPI Evolution air-to-water heat pump

List of indoor unit error codes – De Dietrich HPI Evolution – AWHP-2 MIT-IN-2 iSystem

 

Code Messages Description VéCheck / solution
B00 BL.PSU ERROR The PSU electronic board is misconfigured Parameter error on the PSU electronic board

Set the generator type again in the menu #CONFIGURATION (Refer to

the original rating plate)

B02 BL.S.DEPART The MIT-2 flow sensor is short-circuited or has an open circuit. Poor connection.

Check the wiring between the PCU electronic board and the sensor.

Check that the SU electronic board is properly in place.

Check that the sensor was fitted correctly.

Check the sensor’s resistance.

B08 BL.ENT.BL OUV. The BL input on the PCU electronic board’s terminal block is open. No frost protection. The contact connected to the BL input is open.

Check the contact on the BL.

input

Parameter error.

Check the E.BL.

parameter

Poor connection.

Check the wiring.

 

Code Messages Description VéCheck / solution
B09 BL.ENT.BL OUV. The BL input on the PCU electronic board’s terminal block is open. Frost protection active. The contact connected to the BL input is open.

Check the contact on the BL.

input

Parameter error.

Check the E.BL

parameter

Poor connection.

Check the wiring.

B10 BL.GROUPE.EXT Outdoor unit fault. Refer to the error codes specific to

the outdoor module.

B11 BL.COM SCU Communication error with the SCU electronic board. Poor connection

Check the wiring

SCU electronic board not installed in the unit

Install an SCU electronic board

B12 BL.MANQUE EAU Water pressure is below 0.5 bar Lack of water in the circuit.

Add water to the system.

B13 BL.S.ECS The DHW tank sensor is disconnected or short-circuited Check that the sensor is properly connected to the S.ECS input on the PCU

Check the wiring

Check the sensor’s resistance value. Replace

it if necessary

B14 BL.S.EXT The outdoor sensor is disconnected or short-circuited. Check that the sensor is properly connected to the S.EXT input on the PCU

Check the wiring

Check the sensor’s resistance value. Replace

it if necessary

B17 BL.PCU ERROR The parameters stored on the PCU electronic board are corrupted. Parameter error on the PCU electronic board.

Replace the PCU electronic board.

B18 BL.MAUVAIS PSU The PSU electronic board is not recognized Wrong PSU electronic board for this heat pump.

Replace the PSU electronic board.

B19 BL.PAS DE CONFIG The indoor module is not configured. The PCU electronic board has been replaced.

Set the generator type again in the menu #CONFIGURATION (Refer to

the original rating plate).

B39 BL.DEBIT Low flow. Check the heat pump’s circulator pump setting.

Check that the filter is not clogged.

B40 BL.DEBIT.ARRET Flow fault. Check the heat pump’s circulator pump setting.

Check that the filter is not clogged.

B41 BL.COM.CPT.kWh Communication error with the energy metering option board. Poor connection

Check the wiring

B50 BL.S.DEP.CPT.kWh Energy metering flow sensor fault. Check the sensor’s connection and

resistance

B51 BL.S.RET.CPT.kWh Energy metering return sensor fault. Check the sensor’s connection and

resistance

B52 BL.CPT.kWh.ELEC1 ELEC 1 electric meter fault. Check that the ELEC1 input is not

short-circuited

B53 BL.CPT.kWh.ELEC2 ELEC 2 electric meter fault. Check that the ELEC2 input is not

short-circuited

B54 BL.CPT.kWh.THERM Thermal meter fault. Check that the THERM input is not

short-circuited

 

Code Messages Description VéCheck / solution
B55 BL.DEBIT Low flow. Check the heat pump’s circulator pump setting.

Check that the filter is not clogged.

M04 SERVICE A service visit is requested. The scheduled service date has been reached.

Have the heat pump serviced. To clear the service reminder, set a new date in the #SERVICE menu or set the SERVICE TYPEparameter to NO.

SEC.CHAP.BXXJOURS Screed drying is active.

XX DAYS = Number of screed drying days remaining.

Screed drying is in progress. Heating for the circuits not involved is switched off.

Wait until the number of days shown reaches 0.

Set the SCREED DRYING parameter to

NO.

SEC.CHAP.CXXJOURS
SEC.CHAP.B+C XX DAYS
M23 CHANGE OUTDOOR SENSOR The outdoor sensor is faulty. Replace the wireless outdoor sensor.

 

Code Messages Description VéCheck / solution
B00 BL.PSU ERROR The PSU electronic board is misconfigured Parameter error on the PSU electronic board

Contact the professional in charge of main­

taining the unit

B02 BL.S.DEPART The MIT-2 flow sensor is short-circuited or has an open circuit. Faulty connection.

Contact the professional in charge of main­

taining the unit.

B08 BL.ENT.BL OUV. The BL input on the PCU electronic board’s terminal block is open. No frost protection. The contact connected to the BL input is open.

Contact the professional in charge of main­

taining the unit.

Parameter error.

Contact the professional in charge of main­

taining the unit.

Faulty connection.

Contact the professional in charge of main­

taining the unit.

B09 BL.ENT.BL OUV. The BL input on the PCU electronic board’s terminal block is open. Frost protection. The contact connected to the BL input is open.

Contact the professional in charge of main­

taining the unit.

Parameter error.

Contact the professional in charge of main­

taining the unit.

Faulty connection.

Contact the professional in charge of main­

taining the unit.

B10 BL.GROUPE.EXT Outdoor unit fault. Contact the professional in charge of main­

taining the unit.

B11 BL.COM SCU Communication error with the SCU electronic board. Contact the professional in charge of main­

taining the unit.

B12 BL.MANQUE EAU Water pressure is below 0.5 bar Lack of water in the circuit.

Add water to the system.

B13 BL.S.ECS The DHW tank sensor is disconnected or short-circuited Faulty connection.

Contact the professional in charge of main­

taining the unit.

 

Code Messages Description VéCheck / solution
B14 BL.S.EXT The outdoor sensor is disconnected or short-circuited. Faulty connection.

Contact the professional in charge of main­

taining the unit.

B17 BL.PCU ERROR The parameters stored on the PCU electronic board are corrupted. Parameter error on the PCU electronic board.

Contact the professional in charge of main­

taining the unit.

B18 BL.MAUVAIS PSU The PSU electronic board is not recognized Wrong PSU electronic board for this heat pump.

Contact the professional in charge of main­

taining the unit.

B19 BL.PAS DE CONFIG The indoor module is not configured. The PSU electronic board has been replaced.

Contact the professional in charge of main­

taining the unit.

B39 BL.DEBIT Low flow. Contact the professional in charge of main­

taining the unit.

B40 BL.DEBIT.ARRET Flow fault. Contact the professional in charge of main­

taining the unit.

B41 BL.COM.CPT.kWh Communication error with the energy metering option board. Faulty connection.

Contact the professional in charge of main­

taining the unit.

B50 BL.S.DEP.CPT.kWh Energy metering flow sensor fault. Faulty connection.

Contact the professional in charge of main­

taining the unit.

B51 BL.S.RET.CPT.kWh Energy metering return sensor fault. Faulty connection.

Contact the professional in charge of main­

taining the unit.

B52 BL.CPT.kWh.ELEC1 ELEC 1 electric meter fault. Faulty connection.

Contact the professional in charge of main­

taining the unit.

B53 BL.CPT.kWh.ELEC2 ELEC 2 electric meter fault. Faulty connection.

Contact the professional in charge of main­

taining the unit.

B54 BL.CPT.kWh.THERM Thermal meter fault. Faulty connection.

Contact the professional in charge of main­

taining the unit.

B55 BL.DEBIT Low flow. Contact the professional in charge of main­

taining the unit.

M04 REVISION A service check is requested. The scheduled service date has been reached.

Perform maintenance on the heat pump. To clear the service reminder, set another date in the #REVISION menu, or set the TYPE REVISION parameter to NO.

SEC.CHAP.BXXJOURS Screed drying is active.

XX DAYS = Number of screed drying days remaining.

Screed drying is in progress. Heating for the circuits not involved is turned off.

Wait until the displayed number of days reaches 0.

Set the SECHAGE CHAPE parameter to

NO.

SEC.CHAP.CXXJOURS
SEC.CHAP.B+C XX DAYS
M23 CHANGE OUTDOOR SENSOR The outdoor sensor is faulty. Replace the wireless outdoor sensor.

 

Défaults (code type Lxx or Dxx)

 

 

Code Défaults Source of the

défault

Description VéCheck / solution
D03 D04 DEF.S.DEP.B DEF.S.DEP.C SCU Circuit B flow sensor fault Circuit C flow sensor fault Notes:

The circuit pump is running.

The circuit’s 3-way valve motor is no longer powered and can

be operated manually.

Poor connection Sensor failure

Contact the professional responsible for maintaining the unit

D05 DEF.S.EXT. SCU Outdoor sensor fault Notes:

The setpoint is equal to the parameter MAX MIT.

Valve regulation is no longer ensured, but monitoring of the maximum circuit temperature after the valve is still ensured. The valves can

be operated manually.

Domestic hot water heating

is still ensured.

Poor connection Sensor failure

Contact the professional responsible for maintaining the unit

D07 DEF.S.SYST. SCU System sensor fault Poor connection Sensor failure

Contact the professional responsible for

maintaining the unit

 

Code Défaults Source of the

défault

Description VéCheck / solution
D09 DEF.S.ECS SCU Domestic hot water sensor fault

Notes:

Domestic hot water heating is no longer ensured.

The loading pump is running.

The tank’s loading temperature is equal to the

indoor module’s temperature.

Poor connection Sensor failure

Contact the professional responsible for maintaining the unit

D11 D12 D13 DEF.S.AMB.A DEF.S.AMB.B DEF.S.AMB.C SCU Room sensor A fault Room sensor B fault Room sensor C fault Notes:

The affected circuit operates without input from the room

sensor.

Poor connection Sensor failure

Contact the professional responsible for maintaining the unit

D14 DEF.COM MC SCU Communication failure between the SCU electronic board and the radio module Poor connection

Check the connection and the

connectors

Boiler module failure

Replace the boiler module

D15 DEF.S.BAL.TP SCU Buffer tank sensor fault Note:

Buffer tank heating is no longer ensured.

Poor connection Sensor failure

Contact the professional responsible for

maintaining the unit

D16 D16 DEF.S.PISC.B DEF.S.PISC.C SCU Pool sensor fault circuit B Pool sensor fault circuit C Notes:

Pool heating runs continuously during the comfort

period of the circuit

Poor connection Sensor failure

Contact the professional responsible for maintaining the unit

D17 DEF.S.BAL.2 SCU Tank 2 sensor fault Poor connection Sensor failure

Contact the professional responsible for

maintaining the unit

D18 DEF.S.BAL.SOL. SCU Solar tank sensor fault Poor connection Sensor failure

Contact the professional responsible for

maintaining the unit

D19 DEF.S.COL.SOL. SCU Collector sensor fault Poor connection Sensor failure

Contact the professional responsible for

maintaining the unit

D20 DEF.COM.SOL. SCU Communication failure between the SCU electronic board and the solar controller

Contact the professional responsible for maintaining the unit

D27 DEF.COM.PCU SCU Communication failure between the SCU electronic board and the solar controller

Contact the professional responsible for maintaining the unit

D32 5 RESET:ON/OFF SCU 5 resets have been performed in less than one hour

Turn the heat pump off and back on

 

Code Défaults Source of the

défault

Description VéCheck / solution
D37 TA-S COURT-CIR SCU The Titan Active System® is short-circuited

Check that the cable connecting the SCU electronic board and the anode

is not short-circuited

Check that the anode is not short-circuited

Notes:

Domestic hot water production has stopped but can still be restarted using the button.

The tank is no longer protected.

If a tank without Titan Active System® is connected to the heat pump, check that the TAS simulation connector (supplied in the

AD212 kit) is installed on the sensor board.

D38 TA-S DEBRANCHE SCU The Titan Active System® circuit is open

Check that the cable connecting the SCU electronic board and the anode

is not cut

Check that the anode is not broken

Notes:

Domestic hot water production has stopped but can still be restarted using the button.

The tank is no longer protected.

If a tank without Titan Active System® is connected to the heat pump, check that the TAS simulation connector (supplied in the

AD212 kit) is installed on the sensor board.

D99 DEF.MAUVAIS.PCU The SCU software version does not recognize the connected PCU

Contact the professional responsible for maintaining the unit

L33 DEF.DEBIT The flow is below the threshold set by the parameter DEBIT.MIN.STOP

Contact the professional responsible for maintaining the unit