All Daikin error codes

This page gathers Daikin error codes sorted by type of fault: what each code means, its likely causes, and what you can safely check before calling a professional.
Can’t find your Daikin code in the list?
Describe your issue to Cody. He identifies the code, explains what’s happening, and tells you what you can check yourself. If he doesn’t know the code, he looks it up in the manufacturer’s documentation.

Ask Cody ›

Find your code quickly

The Daikin codes on this page, grouped by type of fault.

communication

E91U4U5U7U8

low pressure

E9031E9032U0U3

power module

P4P4

power supply

E9047

circuit board

PJ

expansion valve

UF

domestic hot water

9A

circuit pressure

W8007

reversing valve

U1

Temperature sensor — Daikin

These codes indicate a sensor that’s no longer returning a consistent value. The fault almost always comes from the sensor itself or its connector, rarely from the unit.

Code 80Medium severityair-to-water
Return water temperature sensor fault
Possible causes
  • Faulty sensor
  • Connector
Models affected: Altherma 3, Altherma LT, EHBH, EHVH
This fault requires a qualified technician. Do not open the unit.
Code 81Medium severityair-to-water
Outlet water temperature sensor fault
Possible causes
  • Faulty sensor
  • Sensor not properly fixed (81-04)
  • Connector
Models affected: Altherma 3, Altherma LT, EHBH, EHVH
This fault requires a qualified technician. Do not open the unit.
Code E9023Informationair-to-water
EC sensor error — tDHW1 or DHW2 tank temperature sensor
Models affected: Altherma 3 ECH2O
Code E9024Informationair-to-water
Pressure sensor — S1NPH pressure sensor on the outdoor heat pump unit
Models affected: Altherma 3 ECH2O
Code E9025Informationair-to-water
Return temperature sensor error — R2T discharge temperature sensor on the outdoor heat pump unit
Models affected: Altherma 3 ECH2O
Code E9026Informationair-to-water
Suction pipe sensor error — R3T suction temperature sensor on the outdoor heat pump unit
Models affected: Altherma 3 ECH2O
Code E9027Informationair-to-water
Aircoil defrost sensor — R5T finned heat exchanger temperature sensor on the outdoor heat pump unit
Models affected: Altherma 3 ECH2O
Code E9028Informationair-to-water
Aircoil temp sensor — R4T finned heat exchanger temperature sensor on the outdoor heat pump unit (11-16 kW installations only)
Models affected: Altherma 3 ECH2O
Code E9029Informationair-to-water
FE cooling sensor error — R6T liquid-side temperature sensor on the outdoor heat pump unit
Models affected: Altherma 3 ECH2O
Code HCMedium severityair-to-water
Domestic hot water tank thermistor fault
Possible causes
  • Faulty DHW tank sensor
  • Sensor improperly positioned in the thermowell
  • Faulty wiring
What you can check
  • Check that the sensor is properly inserted in its housing
  • Turn off power for 30 minutes, then restart
Models affected: Altherma 3, EHVH, EHBH, Altherma ECH2O
This fault requires a qualified technician. Do not open the unit.
Code P7Low severityair-to-air
Swing louver position sensor fault (louver motor)
Possible causes
  • Faulty louver motor
  • Louver stuck
  • Position sensor failure
What you can check
  • Check that the louver isn’t stuck
  • Turn off power for 10 minutes, then restart
Models affected: FTXM, FTXA, FTXS

General fault — Daikin

These codes don’t point to a specific part: the unit is signaling that an internal safety feature has tripped.

Code 8HMedium severityair-to-water
Outlet water temperature abnormally high
Possible causes
  • Insufficient water flow
  • Faulty outlet sensor
  • Setpoint too high
  • Mixing valve stuck
What you can check
  • Check that the circuit isn’t partially closed
  • Bleed air from the circuit
  • Check the outlet temperature setpoint
Affected models: Altherma 3, Altherma LT, EHBH, EHVH
Code A0Critical severityair-to-air
External protection tripped (safety input)
Possible causes
  • External safety input activated
  • External thermostat tripped
  • Faulty safety input wiring
What you can check
  • Check the accessories connected to the safety input
  • Cut power for 30 minutes, then restart
Affected models: FTXB, FTXM, FTXA, FTXF
This issue requires a qualified technician. Do not open the unit.
Code E88Informationair-to-water
Unable to write parameters to external Flash memory. ▪ Contact a technician. — RoCon BM2C board
Affected models: Altherma 3 ECH2O
This issue requires a qualified technician. Do not open the unit.
Code E9006Informationair-to-water
Outlet temperature tv, BH > 65 °C — Outlet temperature sensor tv, BH
Affected models: Altherma 3 ECH2O
Code E9010Informationair-to-water
The jumper on connector “X21A” on board A1P is missing. ▪ Plug in the jumper. — Jumper on board A1P
Affected models: Altherma 3 ECH2O
Code E9021Informationair-to-water
HPSSystem — High-pressure switch S1PH on the external heat pump
What you can check
  • ▪ Faulty high-pressure switch S1PH. ▪ Faulty external heat pump mainboard. ▪ Wiring, poor contact. ▪ Check, replace
Affected models: Altherma 3 ECH2O
This issue requires a qualified technician. Do not open the unit.
Code UACritical severityair-to-water
Incorrect indoor module / outdoor unit pairing
Possible causes
  • Incompatible power modules
  • A module was replaced with an incompatible model
  • Software configuration not performed
What you can check
  • A technician needs to check the compatibility of the part references
Affected models: Altherma 3, EHBH, EHVH, ERLQ, EDLQ
This issue requires a qualified technician. Do not open the unit.
Code UACritical severityair-to-air
Incompatible indoor/outdoor unit combination
Possible causes
  • Incorrect indoor/outdoor unit pairing
  • Incomplete software update
  • Replacement with an incompatible model
What you can check
  • Check model compatibility in the Daikin documentation
Affected models: FTXM, FTXA, RXM, RXA
This issue requires a qualified technician. Do not open the unit.
Code UHMedium severityair-to-water
System addressing error (units not properly identified)
Possible causes
  • Incorrect addressing after installation
  • Board replaced without re-addressing
  • Multiple units sharing the same address
What you can check
  • A technician needs to re-address the system
Affected models: Altherma 3, ERLQ, EDLQ
This issue requires a qualified technician. Do not open the unit.

Communication — Daikin

The indoor and outdoor units are no longer communicating. This is often the connecting cable or a board, not the refrigerant circuit.

Code E91Informationair-to-water
Duplicate bus ID on a CAN module; set a unique data address. — Connected CAN modules
Affected models: Altherma 3 ECH2O
Code U4Medium severityair-to-water
Communication fault between the indoor module and the outdoor unit
Possible causes
  • Connecting cable cut or loose
  • Reversed polarity on the terminal block
  • Interference on the communication line
  • Faulty PCB on one of the two modules
What you can check
  • Check that the connecting cable is tight at both ends
  • Check that polarity is correct
  • Cut power for 30 minutes, then restart
Affected models: Altherma 3, Altherma LT, EHBH, EHVH, ERLQ, EDLQ
Code U5Low severityair-to-air
Communication error between remote control and indoor unit
Possible causes
  • Faulty remote control cable
  • Faulty wired remote control
  • Interference on the remote control line
What you can check
  • Check the remote control wiring
  • Try operating from the infrared remote control
  • Restart the unit
Affected models: FTXB, FTXC, FTXF, FTXM, FTXA
Code U7Medium severityair-to-air
Transmission error between outdoor unit microprocessors (main/inverter) or between outdoor units
Possible causes
  • Outdoor PCB
  • Internal wiring
Affected models: FTXM, FTXA, RXM, RXYM
This fault requires a qualified technician. Do not open the unit.
Code U8Medium severityair-to-water
Transmission error between remote controls (main/sub)
Possible causes
  • Main/sub setting
  • Remote control wiring
Affected models: ERLQ, EDLQ, EPRA
This fault requires a qualified technician. Do not open the unit.

Low pressure — Daikin

The refrigerant circuit pressure is too low. This often indicates a lack of refrigerant, meaning a leak needs to be located.

Code E9031Informationair-to-water
If this error occurs <15 times, reliable operation of the indoor pump is still ensured. ▪ Sporadic message during the unit’s continuous self-monitoring. ▪ No further action needed. If the error occurs 15 times, it causes a lockout and the cause may be: ▪ Current mains overvoltage. ▪ Refrigerant compressor blocked or faulty. ▪ Faulty inverter board on the outdoor heat pump. ▪ Wiring, poor contact. ▪ Service valves not opened on the outdoor heat pump. ▪ Check, eliminate the cause, replace. ▪ Contact a technician if needed. — Electrical component overvoltages
Affected models: Altherma 3 ECH2O
This fault requires a qualified technician. Do not open the unit.
Code E9032Informationair-to-water
▪ Faulty refrigerant compressor. ▪ Faulty inverter board on the outdoor heat pump. ▪ Check, replace. ▪ Contact a technician if needed. — Electrical components
Affected models: Altherma 3 ECH2O
This fault requires a qualified technician. Do not open the unit.
Code U0Critical severityair-to-water
Refrigerant shortage (air-to-water heat pump)
Possible causes
  • Refrigerant leak
  • Incorrect charge at installation
  • Closed service valve
What you can check
  • Check the service valves
  • Do not restart — leak likely
Affected models: EHBH, EHVH, ERLQ, EDLQ
This fault requires a qualified technician. Do not open the unit.
Code U3Critical severityair-to-air
Test run not performed / transmission error
Possible causes
  • Commissioning test not performed
Affected models: RXB, RXM, RXA, RXYM
This fault requires a qualified technician. Do not open the unit.

Power module — Daikin

Code P4Medium severityair-to-air
Inverter heatsink thermistor fault
Possible causes
  • Faulty heatsink thermistor sensor
  • Insufficient cooling
  • Faulty sensor wiring
What you can check
  • Cut power for 30 minutes, then restart
Affected models: RXM, RXA, RXS
This fault requires a qualified technician. Do not open the unit.
Code P4Medium severityair-to-water
Inverter heatsink thermistor fault
Possible causes
  • Faulty inverter heatsink sensor
  • Power board failure
What you can check
  • Cut power for 30 minutes, then restart
Affected models: Altherma 3, ERLQ, EPRA
This fault requires a qualified technician. Do not open the unit.

Power supply — Daikin

The supply voltage is abnormal or absent. Check the dedicated circuit breaker first.

Code E9047Informationair-to-water
Overvoltage
What you can check
  • The system detects an overcurrent to the compressor > 20 A for > 2.5 seconds, 16 times in 5 minutes ▪ Check the compressor. ▪ Check the compressor’s connection and wiring. ▪ Check the operation of the expansion valve (liquid backflow). ▪ Check the refrigerant charge amount and check for leaks. ▪ Check the power transistor. ▪ Check the external inverter PCB. ▪ Check whether the current LED blinks at regular intervals. ▪ Check whether the correct replacement part has been installed. ▪ Check whether the external main board is receiving power. ▪ Check whether the power supply complies with requirements
  • Check for frequency fluctuations
Affected models: Altherma 3 ECH2O
This fault requires a qualified technician. Do not open the unit.

Electronic board — Daikin

A control or power board is no longer responding. A full restart sometimes clears a false fault; otherwise, replacement is needed.

Code PJCritical severityair-to-water
Capacity setting error (power board)
Possible causes
  • Board replaced without capacity configuration
  • Capacity jumper incorrectly positioned
  • Incorrect indoor/outdoor unit pairing
What you can check
  • Technician visit required for reconfiguration
Affected models: Altherma 3, ERLQ, EDLQ, EPRA
This issue requires a qualified technician. Do not open the unit.

Expansion valve — Daikin

The electronic expansion valve no longer regulates refrigerant flow.

Code UFMedium severityair-to-air
System not configured / wiring-piping mismatch
Possible causes
  • Wiring and piping swapped between units (multi-split)
  • Shut-off valve closed
  • Refrigerant shortage
Affected models: RXB, RXC, RXF, RXM, RXA, RXS

Domestic hot water — Daikin

The domestic hot water circuit is faulty: tank sensor, three-way valve, or backup heater.

Code 9AMedium severityair-to-water
Domestic hot water tank circuit fault
Possible causes
  • Faulty DHW tank sensor
  • Stuck 3-way valve
  • Failed DHW backup heating element
What you can check
  • Cut power for 30 minutes, then restart
Affected models: Altherma 3, EHVH, EHBH, Altherma ECH2O
This issue requires a qualified technician. Do not open the unit.

Circuit pressure — Daikin

Code W8007Informationair-to-water
Warning: water pressure has exceeded the maximum allowed value. ▪ Faulty membrane expansion tank or incorrectly set pre-charge pressure. • Check, replace. ▪ [Max Pressure] setting too low. • Adjust the setting if needed. If the setting is correct, • drain some water to reduce the system pressure. — Water pressure in the heating system is high
Affected models: Altherma 3 ECH2O

Reversing valve — Daikin

Code U1Critical severityair-to-water
Phase reversal or missing phase (three-phase power supply)
Possible causes
  • Two phases swapped at connection
  • A missing phase
  • Blown phase fuse
  • Partially tripped circuit breaker
What you can check
  • Check the electrical panel and fuses
  • Have an electrician check the phase order
Affected models: three-phase Altherma 3, three-phase ERLQ, three-phase EPRA
This issue requires a qualified technician. Do not open the unit.